Loading...
Ordinance 714 PART XII of the BUILDING CODE I OF THE CITY OF MIAMI BEACH, FLORIDA 'F? Adopted June 28th, 194. 12. 25.01 INDEX 12.01.07) 12.08.02) Accepted Standards 12.16. 24 Accessibility 12.03.07 Age Limit 12.08.03) Air Gap - Definition 12. 23.15) Air Gap - Flushometer 12. 21.02 Air Gap on Closet Bowls 12.08.06 Alignment 12. 22.09 Alterations 12. 25.16 Alternate Materials 12.06.16 ) 12.16. 22.10) Apparatus using Water where Food is Contained 12. 27.04 Apartments (Homes) See State Rule No. 1405 12. 34.04 Appeal - Owner 12. 34.05 Appeal - City Council 12.04.01 Application 12. 26.04 Application 12.08.04 Approved 12.05.06 Approval of Plans 12.03.06 Apprentice 12.08.05 Area Drain 12.08.07 A. S. T. M. 8. 33.01 Automatic sprinkler 12.06.18 Back Flow of Sewerage 12.08.08 Back Flow 12.08.09 Back Vent 12. 22.05 Back Syphonage 12.06.01 Basic Plumbing 12.16.17 Basement ( Note Cellar) 12. 33.05 Bath Room - Ventilation 12. 21.10 Bath Tubs 12. 21.05 Bath Tub and Shower Connections 12. 32.09 Baptistries and Lily Ponds 12.16.18 Bar Wastes 12.16.19 Bar and Fountain Wastes 12.30.08 Blow Off 12.01.05 Board. of Examiners 12. 27.07 Boarding House 12. 30.13 Boiler Inspection 8. 34.03 Boilers - Low and High Pressure 12.08.10 Branch 12.08.11 Branch Vent 12.1 .17 Brass and Copper Pipe 12.18.18 Brass and Copper Tubing 12.18. 27 Brass Floor Flange 12.06.05 Building Connected to Sanitary Sewer 12.06.06 Building Connected to Septic Tank 12.08.12 Building Drains - Definition 12.08.13 Building Drainage System 12.05.02 Building Location on L t 12.16.04 Building - More Than 8ne to a Lot .,, f \, 12.08.14 Building Main -- 12. 26.04 Building Permit before Plumbing 12.10.01 Building to be Inspected before Occupancy 12.06.02 Building Not to be Used Before Certificate of 12. 4.11 II II II If u II 3 � Occupancy 12.06.05 Building Connected to Sanitary Sewer 12.08.15 Building Sewer 12.08.16 Building Sub-drain 12.16. 21 Bubbler end Drinking Devices 12.18. 27 Caulking Ferrules 12.18. 24 Caulking Ferrules - Sizes 12.16.10 Caulking Joints 12.09.01 Catch Basin 12.13.12 Cast Iron Soil or Vent Pipe 12.16.17 Cellar Floor Drain (Basement) • 12. 20.07 Cellar Fixture Requirements 12. 20.0 Cellar Fixture Sewerage Lift 12. 20.09 Cellar Fixture Discharge from Tare 12.03.02 Certificate of Occupancy 12.03. 02 Certificate Renewals 12. 22.07 Cesspools - Prohibited 12.16.12 Change in Direction 12.16.13 Change in Vertical Direction - 12.18.02 Change in Horizontal Direction 8. 33.05 Check Valves 12. 23.08 Check Valves 12. 30.05 Check Valves 12. 23.03 City Curb Cocks 12.09.02 Circuit Vents 12. 23.02 City Water Supply 12. 22.02 Closet Floor Connection 12.21.02 Closet Bowl Air Gap 12.16.14 Closet Connection 12.06. 10 Clean Outs 12.09.03 Clean Outs 12.16.13 Clean Outs 12.09.06 Combination Fixtures 12.09.05 Conductors or Leaders 12.09.08 Continuous Waste 12.09.07 Continuous Waste and Vent 12.16.14 Connection between Soil and Lead 12.16. 02 Connection to Sanitary Sewer 12. 34.02 Condemnation 12. 34.03 Condemnation Notice 12. 27.10 Conflict with Principal 12.10. 22.03 Coffee Urns 12.09.04 Code 12.18.05 Cross Connections 12.09.09 Cross Connections 12.01.04 . Collection of Fees 12.09.10 Dea.. End 12. 25.08 Defective Material 12. 25.09 Defective Fixtures 12.08.01 Definition of Terms 12.09.11 Developed Length 12.19.03 Dental Cuspidors 12.18. 10 Depth of Soil Pipe to Septic Tank 12.09.12 Diameter 12.34.12 Display Sign of Registration 12.11.05 Downspout - see Leaders or Hoof Drains 12.1(',.01/1- Double Sanitary Tees 12.03.13 Drains 12.20.04 Drains - Floor 12. 20.05 Drains -- Floor 12. 20.06 Drains - House 12.09.14 Dry Vent 12.09.15 Dry Well 12.16.16 Drainage Fitting 12.06.08 Drainage System shall be Designed 12.22.16 Drainage Elevation or Tunneling 12. 27.09 . Drink Stand 12. 20.09 Drainage from Basement or Cellar 12. 27/03 Duplex 12.09.16 Dual Vent 12. 22.01 Earthenware with Metal Floor Connection 12.10.01 Ejectors closet bo- __ 12. 25.01 Emergency York 12.03.01 Examination of Plumbers 12.03.08 Examination Dates 12.01. 05 Examination Board 12,03.09 Examination Certificates -. Renewals 12.03.10 Examination Renewal of Fees 12. 22.16 Excavations - see Drainage or tunneling 12.01. 04 Fees - Collection of 12.28.01 Fees for Plumbing Installation s 12. 28.02 Fees for Septic Tanks t 12. 28.033 Fees for Steam Installations 12.28.0 - Fees for Hot Water Installations 12. 28.05 Fees for Solar Heating Installations 12. 28.06 Fees for Refrigerator Installations 12. 28.07 Fees for Oil Burner Installations 12. 28.08 Fees for Well Installations 12. 28.09 Fees for Swimming Pool Installations 12. 23.10 Fees for Sprinkler System Installations 12. 28.11 Fees for Ventilation Installations 12. 28.12 Fees for Renewal Installations 12.10.02 Ferrules 12.10. 2 Ferrules - Caulking; 12.10. 24 Ferrules - Sizes 12.10.07 Flood Level 12.10. 27 Floor Flange - Brass 12. 22. 02 Floor Flange - Gasket 12.20.04 Floor Drain in Kitchen 12.20.05 Floor Drain in Public Toilet Rooms 12. 20.06 Floor Drain in Cellar 12.06.03 Flushing of Fixtures 12. 23.14 Flushometers 12. 21. 02) Flushometers 12.07.03) Flushometers 12. 23. 1 5) Flushometers - Air Brake 12.10. 04) Fixtures 12. 21.01 ) Fixtures 12. 21.12) Fixtures 12. 22.04 Fixtures - Accessories 12.17. 32 Fixtures - At base of Stack 12. 22. 06 Fixtures - Contents 12.10.05 Fixtures - Drains 12. 21.07 Fixtures - Earthenware 12.06.11 Fixtures - Trap 12. 17.03 Fixtures - Highest Fixture Vent Fixtures Recuirea - See Rule No.l401 .Fle. State Rule 12. 22.0) Fixture - Alera:tions or Replacement 12.22.05 Fixture - Supply and Back Syphonage 12. 22.03 Fixture - Quality - See Rule No. 1447.Fla State Rule 12.07.01 ; Fixture Units 12.10.06) Fixture Units 12.17.13 Fixture - Ventilation 12.10.03 Fittings 12.10.00 Free Circulation of Air 12.32.07 Filters - Swimming Pool 12. 3 .01 Fire - Stand Pipes 12.02.02 Gas - Ordinance #524 Gas Master See Ordinance #524 Gas Fitter II n 12.04.01 Gas Permits " " 12.04.01.02 Gas License " it 0. 3 .02 Gas Space Heaters - also see Fla. State Rule 12.10.10 Garages - Private 12.10. 0; Garages - Public . 12.20. 01 Garages - Oil end Grease Traps 12. 22.02 Gaskets for Water Closet Floor Flanges 12.02.03 General Laws of Florida Pertaining to Plumbing' 12.16. 22.0 - Glass Water Service 12.10. 11 Grade 12.05.07 Granting of Plumping Permits 12.1 .0r Grease gaps 12.1).00 Grease Trap - Waste Vent 12.1).09 Grease Trap - Location 12.1;.10 Grease Trap - xecuirements 1 ^_ 1 ^. 11 Grease Trap - Accessories 12.15.16 Grease Traps - Accessibility 12.15.12 Grease Traps - Desin 10.15; .16 Grease Traps - Efficiency 12.19.15 Grease Traps - Control of Flow 12.19.17 Grease Traps - Table 12.19.05 Grease Traps - Interceptor 12.19. 06 Grease Traps -- Vent 12.15. 05 Grease Traps - Water Jacket 1% 22.10 Hangers and Supports 12. 22.11 Hangers - Stack Supports 12.30.01 Heeting - Steam 8.34.03) Kish Pressure Boilers 12.30.11 ) High Pressure Boilers 12.046.01.02 Hot Water - License 12.30.00 Hot Water Heater Protection 8, 34. 06•) Hot. Water Heater Protection 12,27.05 Hotel - Sanitary Requirements (See Fla. State Rule 12.10. 12 Horizontal Branch No.1401-1 ) 12.1& 02 Horizontal Soil 12.16. 20 Hydraulic Machinery 12.16.06 House Lateral 12.16.11 ) House Connec tion 12. 26.09 ) 12.10.1 3 House Drain 12.10.1 -) House Sewer 12.13.16) House Sewer 1°.06.16) Ice Box 12.16. 22.01 Ice Box 12. 25.08 Imperfect Materials 12.35.01 Index of Plumbing 12..16.12 Identification of - aterials 12.06.09 Identification of Materiels 12.11.01 Indirect Wastes le,1 22 Indirect or Sfe Pastes 12.16. 23 Indirect ';tastes Limit 12.11.02 Interconnection 12.11.04 Interctnnection 12.11.03 Interceptor - aee Sand Trap 12.25.02 Inspection Notice 12. 25.04 Inspection - Time for 12. 25.05 Inspection 12. 25.06 Inspection for Rough 12. 25.11 Inspection for Finish ' 12.16 . 14- Joints in Fixture Connections 12.16. 10 Joints in Cast Iron 12.03.05 Journeyman Plumbers - See Fla. State pule #1430. 12. 20.04 Kitchen Floor Drains 12. 21.03 Latrines or Range Closets 12.16.15 Lead Bends - Waste Entering same 12.13. 25 Lead Caulking 12. 16.14 Lead - Connections with Soil Pipe 12.1: . 19 Lead - Pipe Requirements 12. 22.17 Lead - Pipe Protection 12.18. 20 Lead Pipe Sizes 12.1:). 21 Lead - Sheet 12.11.05) Leader - See Root Drain 12. 22. 14 Leader 12.16.04 Lot or Plot Vent Requirements 12.05.02 Location - Lot, Bloc, etc. 12.30.12 LowPressure Boilers 12.1 . 01 Long Sweep Bend's 12.11.06 Long Sweep 12.11.07 Logp Vents 12.01.05 License of Plumbers 12.04.01 .01 License of All Trades 12.03.0) ) License Renewals 12.03.10) License Renewals 12.23.01 Main 'deter Supply 12.13.06 Main Sewer, or House 12.16.11) Mein Sewer, or House 12:11. 09 Main Vent 12.11.0 8) Manhole 12. 21.0) Manhole 12.03.0+ Mester Plumber 12. 23.05 Materials - Water Supply 12. 16.05 Materials - quality (House, sewers and drains ) 12. 25.08 Materiels - Defective ( see quality) 12.11. 10 Non-Pressure Drainage 12. 34.09 Notices 12.25.10 Notice to Building Inspector 12. 34.02 Notices of Condemnation 12. 23.04 Notices to deter Department 12.18. 25 Nipples - Soldering 12.16.01 Occupancy - Building must be inspected 12. 2r 11 Occupancy for Human Habitation 12.34.11 Occupancy not allowed 12.11.11 Offset r 12.28.07 ) Oil Burner Equipment 12. 31.01) Oil . Burner Equipment 12. 31.01 0i1 Burner Contractor' s License 12.31.02 - Oil Burner Inspection 12.31.03 Oil Burner System 12. 0.01 Oil Interceptor. 12. 20.02 "il Interception Specifications 12.04.01 Oil Permits 12.04.01.02 Oil License 12. 74.04 Owner Appeal 12.34.07 Owner Shall Comply 12.23.10 Owner' s Responsibility 12. 25.15 Overflow Pipe 12.34.14 Penalties 12. 24.01 Penal (Cost of doing plumbing without permit ) 12.05.01 Permit must be Obtained 12.04-.01 Permits 12.05.06 Permit Violations 12. 26.05 Permits Not Required 12.04-.03 Permits for Steam 12.04 .04 Permits for Hot Water 12.04.01 Permits for Plumbing 12.04.06 Permits for Septic Tanks 12.04.07 Permits for Refrigeration 12.04. 05 Permits for. Solar Systems' 12. 28.13 Permit Records 12.0?'-.08 ) Permits for Oil Burners 12.31.01 ) Permits for Oil Burners 12.04.09 Permits for Gas Piping 12.014.10 Permits for Wells 12.04. 11 Permits for Swimming Pools 12.04-.12 Permits for Sprinklers 12.O4.13 Permits for Ventilation 12.04.14 Permits for Kitchen Ventilation 12.04-.15 Permits for Similar Trades 12.05.05 Plans - Approval 12.05.04 Plans Recuired (plumbing) 5.10.17 Plumbing - General Recuirements 1 l3 5.14-.1 5.15.14 5.16.11 5.17. 11 5.18. 12 5. 19. 11 5. 20. 11 7. 30. 20 Section XIV -Florida State Rule No. 1401 12.12.01) Plumbing - Definition 12.02.01 ) ii II 12.03.12 Plumbing - Chief Buildinry Inspector' s Supervision 12.06.07) Plumbing Fixtures - non-absorbent 12.12.02) Plumbing Fixtures 12.04. 02 Plumbing, Permits - also Fla. State Rule #1401 & 1402 1.02.02 Plumbing Permits 12.0 -.01.02 Plumbing License 12.12.03 Plumbing System 12.01. 03 Plumbing State Recuirements -Rules X1401 to 1454 4 12.17.1.1 Pipe - Change to -Vertical 12.18. 02 Pipe - Change to Horizontal 12.18.06 Pipe in Concrete 12.18.0Pipe in Grade Beams and Columns 12.18.09 Pipe in Spread. Footings 12.18.07 Pipe in Columns 12.16.07 Pipe ,in Fireproofing- Fla. State rule #1Li13 12.16.07 Pipe in Masonry 12.18.18 Pipe. in Brass one. Copper (Soil.) 12. 22. 12 Pipe Supports 12.16.12 Pipe - vertical Direction 12.12.011-. Pool - Definition 12.12.05 Pressure Drainage 12. 23.07 Pressure Valves and Temperature 12.12.06 Primary Branch 12.12.07 Privy 1126.01 Privy Vaults 1?. 26.02 Privy Permits 12. 26.03 Privy Maintenance 12.06.15 Preventive Measures 12.25.12 Protection to Water Tanks 12. 25.13 Protection to Electrical Machinery 12. 22.0 Prohibited Connections 12.18.03 Prohibited Fittings 12.04.01 Pump or Well Permits 12.04.01.02 Pump or Well License 12. 32.07 Pumps and Filters 12.04 . 10 12.12.08 Public Buildings 12. 26.09 Public Sewer - see sewer 12. 27.01 Public Toilet Room 12.01.02 Purpose , 12.18.11 Quality of Materials 12.18.14 Quality of Sewer Pipe or Soil Pipe 12.16.05 Quality of Pipe 12.18.14 Quality of Pipe 12.18.17 Quality of Copper and Brass Pipe 12.18.18 Quality of Copper and Brass Tubing 12.18.18 Quality of Steel 12.18.15 Quality of Wrought Iron Pipe 12.1 .19 Quality of Lead Pipe 12. 22.03 Quality of Fixtures 12.18.11 Quality of Materials 12. 22.14 Rain Water Leaders 12. 22. 17 Ret Proofing 12.21.08 Range Closets 12.16. 20 Receptacle where Bottled Goods are Stored in Ice 12.16. 22 Receptacle Where Food is Stored 12.30.07 Reducing - Pressure Valve 12.28.13 Records 12.06.16) Refrigerators 12.16. 22) xefr•igerators 12.30.07 Reducing - Pressure Valve 12. 28.13 Records 12.06.16) Refrigeration 1246.Q1)02 refrigeration License 12.0-1 .O1 Refrigeration Permits 12. 20.12 Refrigeration Pipes 12. 20.11 Refrigeration Trap 12. 20.11 Refrigeration Waste Size 12. 20.12 Refrigeration paste 12.03.11 Registration of Plumbers 12. 3 -.12 Registration shall be Displayed 12. 23.06 Relief Valves 12. 34.10 Removal Notices 12.13.10 Relief Vent 12.03 09 Renewal of License 12.22.09 Repairs 1^ 26.06 Repairs 12. 29.12 Repair Permit 12. 30.06 Responsibility of Owner or Plumber 12. 27.08 Restaurants - Fla. State Rule # 1 -07 12.12.11 Riser 12. 22.14 Roof Drain 12. 22,13 Roof Flashings 12.17. 35 Roof Terminals 12. 17. 36 Roof Extension 12. 27.0 Rooming oHouses - see Fla. State Rule # 1 +06 omin 12.1°,12 Roughing 12. 25.05 ) Roughing Test Inspection 12.25.06) RoughingTest j-nspg.ction 12,12.13 Rural or Isolated. lumbing l2.09.0 Rules and Regulations (Code) 12. 23.06) Safety Valves t 1^. 23.07) 12. 23.Of) 12. 23.10) 12. 29.13 12.30. 0.'2,, 12. 30.16 12. 23.00 12.16.0 12.30.07 Safety - Hot Water Boilers 12.30.08 ) Safety - Steam 12. 30.11 ) 12.30.12) 12. 29.13 Safety , - Solar Heaters 12.13.01 Sef ing Sandwich Stand (See Fla. State Rule #1401) 7. 30. 20 Sanitation of Temporary Buildings 12.1',.05 Sanitary Sewer 12.15.0D Sanitary Requirements of all lots 12.06.19 Sanitary Requirements of Buildings, Stores, etc. 12. 27 01 Sanitary Requirements of Buildings, Btores, etc. 12. 27/02 Sanitary Recuirements - Single Family 12.06.19 Sanitary Maintenance 12. 20.03) Sand Interceptor 12.13.02 ) Sand Interceptor 12. 20.03) Sand Traps 12.13.02 Send Traps 12.13.03 Sewer - Sanitary - Definition 12.16.02 Sewer for Each Lot 12.13.06 Sewer - House 12. 26.09 Sewer Connection 12.16.03 Sewer Vents 12.13.04 Septic Tank - Definition 12. 26.07 Septic Tank - Permits 12.04.01.02 Septic Tank License 10. 26.08 Septic Tank Requirements - See Fla State Rule #1450 12. 26.10 Septic Tank Location 12. 26.0 Septic Tank Size 12.13.08 Shall 12.1 . 21 Sheet - Lead. (look up 'leadt ) 12. 21.0 r Shower - Outside 12. 21.05 Showery Inside 12. ?1.06 Shower - Cabanas 12. 27.02 Single-Family Requirements 12. 27.11 Size of mater Pipe 12.07.02 Size of Sewer Pipe 12.07. 02 Size of Soil Units 12.07.03 Size of Vent Units 12.0A.15 Similar Trades 12.04.01 Similar Trades - Permits and license 12.13.07 Side Vent 12.13.09 Siphonage 12.15. 10 Siphonage - Back 12.17. 35 Siphonage - Protection against, Trap Siphonage 12.07.01 Sinks -( See Fla. State Rule # 1 +47) 12. 21. 11 Sinks 12.07.01 Sinks - Slop 12.19.10 Sinks - Connected to Grease Traps 12.13.1 _ - Slip Joints, 12.16.19 Soda Fountains 12.16.18 Soda Fountain Vents 12.16.15 Soda Foundain Waste 12.13'.11- Soil Pipe Weight 12.16.11 Soil - Sewer or House Drain 12.13.12 Soil Pipe - Note Fla State Rule r= 1116 12.16.09 Soil - Waste and Vents 12. 27.09 Soft Drink Stands or Fruit Juice Stands 12. 29.01 Solar Systems 8. 23.10 Solar Water Heaters 12. 29.01 Solar Water Heaters 12. 29.02 Solar Heater Contractors 12.04.01.02 Solar Water Heater License 12.04.01 Solar Water Heater Permits 12. 29.03Solar Water Heater - Definition 12. 2 .04 Solar Water Heater Erection 8.34.01 Solar Water Heater Coil Boxes 12. 29.05 Solar Water Heater Coil Boxes 12. 29.06 Solar Water Heater Supports 8. 34.02 Solar Water Heater Tanks 12. 29.07 Solar Water Heater Tanks 12. 29.08 Solar Water Heater Floor Plates 12. 29.09 Solar Water Heater Tank Box 12. 29.10 Solar Water Heater Tank Insulations 12. 29.11 Solar Water Heater Tank Box Construction 12. 29.12 Solar Water Heater Repairs and Replacements 12. 29.13 Solar Water Heater Supply and Relief Valve 12.18. 25 Soldering Nipples 12.18. 26 Soldering Bushings 12.13.13 Spigot. 8.33.03 Stand apes 12.044.01 Sprinkler Permits 12.04.01.02 Sprinkler License 8. 33.01 Sprinkler Systems 12.13.11 Stack 12.13.15 Stack Vents 12.13.15 Stack Supports 12.01.0State Requirements -See section XIV, Rule #1401 12.05.04 State Hotel Requirements for Plumbing & Gas 1 2. 30.01 Steam Fitting 12.04.03 Steam Fitter License 12. 30.02 Steam Fitter License 12. 30.02 Steam Fitter Permits 12.30.03 Steam Fitter Master 8.34.03 Steam Boiler 12.30.04 Steam Boiler 12.04.01.02 Steam Boiler License 12.04.01 Steam Heating 12.18.16 Steel Pipe , 12.16. 22.08 Sterilizer 12.13.16 Storm Sewer 12.27.01 Store Connection 12. 23.12 Stop on Water Lines - See Fla. State Rule # 1411 12. 23.13 Stop on Hotel Bath 12. 23.13 Stop on Apartment House btop on Fire Lines - Note Building Code. 12. 22.04 Supplies - Back Siphonage 12.13.17 Sump 12. 20.09 Sump Vent Pipes 12.03.12 Supervision of Plumbing 12. 22.14.02 Surface or Seepage of water - Fla State Rule #1444 12. 32.01 Swimming Pools 12.04.01.11 Swimming Pool Contractor' s License _ 12. 32.02 Swimming Pool Contractor' s License 12.04.01 Swimming Pool Permits 12.32.01 Swimming Pools - State Health Department 12. 32.08 Swimming Pools - Drain 12. 32.03 Swimming Pools - Drainage 12. 32.05 Swimming Pools - Cross connections 12.32.07 Swimming Pools - Filters 12. 32.04 Swimming Pools - Regulators 12.32.06 Swimming Pools - Water Supply 12.07.01 Tables - Unit 12.19.17 Tables - Grease 12. 26.11 Temporary Toilets 7.30. 20 Temporary Toilets - Building Code 12.06.14 'test - See Fla State Rule No. 1408 12. 25.05 • Test 12. 25.06 Test - Rough 12. 25.07 test - Approval 12.16.08 Terra Cotta. - Sewer Under k3uilding 12.16.06 Terra Cotta - Connection Between Cast Iron 12.14.01 Terminal 12. 25.04 Time for Inspection 12.1.4.02) Traps - Definition (Note Fla State Rule # 1432) 12.19.01) Traps - Distant from Vents 12.19.02 Traps - Fixtures - Fla State Rule # 1432 12.19.03 Traps - Dentist Cuspidor 12.17.11 Traps - Vent Limit - Fla State Rule # 1434 12.14.03 Traps - Crown 12.14.0 Traps - Seal 12.14.05 Traps - Depth of Seal 12.].4.06 Traps - Deep Seal 12.14.07 Traps - Drum 12.13.02 Traps - Sand 12.14.08 Traps - Sand 12.19.04 Traps - Grease Vent 12.19.06 Traps - Grease Vent 12.19.07 Traps - Grease (for sink) 12.19.08 Traps - Grease (waste) 12.19.09 Traps - Grease (location) 12.19.10 Traps - Grease (requirements) 12.19.11 Traps - Grease (accessories) 12.19.12 Traps - Grease (design) 12.19.03 Traps - Grease (interior) 12.19.1 Traps - Grease (accessibility) 12.19.15 Traps - Grease (water jacket) 12.19.16 Traps - Grease (efficiency) 12.19.17 Traps - Grease (table) 12.19.1 Traps - Grease (control of flow) 12.19.05 Traps - Interceptor 12.06.12 Traps - Siphonage 12. 20.01 Traps - Oil and Grease 12.7., .03 Top. Fixture Vent. ( see fixture) • 12.06.02 Toilets - Requirements in Buildings, etc. 12.07.01 Toilets - Recuirements in Buil(f_ings, etc. ...,- 12. 22.16 Trenches for Pipes 12.01.01 Title 12. 25.1 - Transformer Room Requirements 12. 22.16 Tunneling Under Side Walls 12. 27. 02 Units - Soil and Waste 12.07.03 Units - Vents 12. 21.09 Urinals - Note Fixtures (Fle.Atete Rule # 1411-7 D) 12.07.01 Units - Tables 12.07.02 snits - Vents 12.07.03 Units - Vents 12.34.10 Unlawful to Remove Notice 12.34.11 Unlawful to Occupy 12. 31-.06 Unsanitary - Plumbing 12. 23.08 Valves - Check 12. 23.12 Valves - Stop 12. 23.06 Valves - Relief 12.01.06 Validity 12.15.01 ' Vents ;y 12.15.02 Vents - Bac_: 12.07.03 Vents - Units capacity 12.17.01) Vents Wet 12.15.04) Vents - Wet 12.17. 20 ) Vents - Yoke 12.15.05 ) Vents - Yoke 12.15.06 Vents - Local ' 12.17. 33 Vents - Main 12.17. 37 Vents - Location Adjoinin12, Tall Building 12.1;.03 Vents - Unit definition 12. 31 .01 Vents - Flues - pipes 12.17. 34 Vents - Table 12.17. 35 Vents - Crown 12.17. 35 Vents - Terminal 12.17. 30 Vents - Extension 12.17. 37Vents - Height of tjoining,,Building 1.17. Vents - Protection to Trap 6ea.l 12.17. -0 Vents - Increases 12.17. 41 Vents - Change in Vertical 12.17.02 Vents - Re-vent 12.17. 32 Vents - Fixtures Base of Stack 12.17. 03 Vents - Highest Fixture , 12.17.0r Vents - Through Roof 12.17.05 Vents - Prohibited 12.17.06 Vents - Horizontal 12.17.07 vents - Septic Tank — 12.17.08 Vents - Sewage System 12.17.09 Vents - Connections 12.17.10 Vents - Stacks 12.17.11 Vents - Distance from Trap 12.17.12 Vents - Relief (back) 12.17.12 Vents - Fixture 12.17. 14 Vents - Minor ."' 12.17.1 Vents - Major 12.17. 2 Vents - Relief 12.17.16 Vents - Dual 12.17.17 Vents - Dual Fixture 12.17. 21 Vents - Group 12.17. 22 Vents - One Bath Group 12.17. 23 . Vents - One Beth Group 12.17.18 Vents - Two Bath Groups 12.17.19 Vents - Four Fixture 12.17. 25 Vents - Circuit or Loop 12.17. 26 Vents - Branch Interval 12.17. 27 Vents - Duel Relief 12.06.13 Vents -- location 12.17. 28 Vents - Limits of Circuit (Note Table) 12. 17. 29 Vents - Limits of Circuit Table 12.17. 28) Vents - Loop Limits 12.17. 25 Vents - Loop Limits 12.17. 30) Vents - Loop Limits 12.17. 31 Vents - Double Battery 12.1 .02 Vertical I`iping • 12. 3 7.01 Ventilation 12.04-. 01.02 Ventilation 12. 33.02 Ventilation Contractor' s License 12. 33.03 Ventilation Fees 12.0'.01 Ventilation Permits -- 12. 33. 04 Ventilation Flans 12.06.17 Ventilation Light and Air 12. 33.06 Ventilation Kitchen 12. 37.05 Ventilation Bath Room 12. 3 .01 Ventilation Hood 12. 3='.08 Ventilation Gas Appliances 12. 34.14 Violations end Penalties 12. 34.13 Violation of Permit Application 12.18.13 Vitrified Clap Pipe and Joints l2. 3 -.08 WarninP, 12.15.07 Waste Pipes 12.07.02 Waste Pipe - Units Capacity 12.16.15 Waste Entering Lead Bends 12.11.01 Waste Indirect 12.16.1s Waste - Bar and. Fountain t 12. 20.10 Waste - Refrigerator 12. ^0. 11 Waste - Refrigerator size 12.16. 20 Waste - Over Hydraulic Machinery 12.07. 01) Water Closet Fixture 12.16.04) Water Closet Fixture 12. 21.07 Water Closet Fixture 12. 22.02 Water Closet Floor Gasket 12. 32. 09 Water Column 12. - . 31 Water Service Connection 12. 2- . J2 Water Flush Valves 12.21. 01 Water Closet T -nks 1% 03. 15 Water Closet Tank Stops 12. 25.05 Water Closet Test -- 1^.15.08 titter- Supply - See Fla State Rule #11.09 & 111-15. 8. 33.05 Water Supply to Stand Pipe or Sprinkler Y12. 15. 09 Water Distribution 12. 23.05 Water Materiels 12. 03.0° Weter Department Rules 1`", ` " .01 Water Service Pipe 1."._ Water Treatment Devices . 12. . � _ Water - Size of Supply to Fit re 12.- _ . 22 Water Still 12. 23. 02 Water - Ap: lic?tion to dater Department 12. 23.09 Water Meter Protection . 3 .0; W-ter Heaters 12.21.12 Wash Trays 12.0'1 .01 ) Wells and rumps 12.04.C1.02) Wells and Pumps - ^.31 .10) Wells & Pumps 12.15.10 Wiped Joints 1°,25.03 Work left Uncovered 12.15.11_ Workmanship 12.i_.15 i' rou t Iron Pipe 1-.17. 20Yoke Vents 1. 33.05 Yard Sprinkler % 33.04 Yard Hydrants ORDINANCE NO. 7l AN ORDINANCE AMENDING SECTION 2 OF ORDINANCE NO. 592 OF THE CITY OF MIAMI BEACH, FLORIDA, KNOWN AND DESIGNATED AS THE "MIAMI BEACH BUILDING CODE" , BY ADDING THERETO, AT THE END THEREOF,AN ADDITIONAL PART TO BE KNOWN AS PART XII. BE IT ORDAINED BY THE CITY COUNCIL OF THE CITY OF MIAMI BEACH, FLORIDA: SECTION 1. That Section 2 of Ordinance No. 592 of the City of Miami Beach, Florida, known and designated as the "Miami Beach Building Code" , be and the same is hereby amended by adding thereto, at the end thereof, an additional Dart to be known as Part XII , and to read as follows: PART XII PLUMBING CODE OR REQUIREMENTS 12.01.01 This Part. XII of the Building Code of TITLE the City of Miami Beach, Florida, shall be known as the Plumbing Code and may be cited as such, and will be referred to hereinafter as the Plumbing Requirements or Code. 12.01 02 The purpose of the Plumbing Requirements or PUr.POSE Code is to provide certain accepted standards, basic requirements, provisions and require- ments for safe and stable design, methods of construction and use of materials in buildings, premises and/or structures hereafter erected, constructedT enlarged, altered, repaired, moved, or converted to other use; to regulate the equipment and materials used within buildings, premises and structures within the City of Miami Beech, Florida. 12.01.03 To comply with the State of Florida. Hotel Com- FLORIDA mission rules and regulations governing install- STATE ation of plumbing within hotels, apartment REQUIRE- houses, rooming houses and restaurants and also MENTS regulations governing master plumbers, journeyman plumbers and gas fitters , ( see Florida State Hotel Commission Rules, section 14, rules No. 1401 to No. 1454) , establishing basic principles for plumbing, water supply systems, for fire and com- mercial use, hot water, steam or steam heating equipment and piping, waste, .ddrainage, soil, sewer, and vent pipes; establishing requirements as to connections with the city water supply, or water supply pipes and fixtures, sanitary sewers, sewage treatment tanks, septic tanks, supply and discharge wells, privies, gas piping, (either manufactured or bottled) or other gas containers, gas appliances, oil pining and appliances, s,Timm- ing pool installations, sprinkler systems ea all types, refrigeration, solar water equipment anc_their installation. 1:_.01.04 For the issuance of permits, collection of COLLECTION fees, issuance of occupational license or OF FEES certificates, requirements of plans and specifications, establishing the duties and authority of the Chief Building Inspector, Chief Plumbing Inspector and his deputies. . 12.01.05 Providing for the appointment of a Board of BOARD OF Examiners consisting of four (4) examiners EXAMINERS as per section 1. 03.05.03 of the Building Code; examination of applications for master plumbers, journeyman plumbers and registration of all persons engaged in aforesaid trades or occupation; the issuance and revocation of licenses; establishing rules and regulations for inspection and tests; providing for the enforcement of ordinances referring to sani- tary laws of the City of Miami Beach, Florida. r- 12.01.06 Providing that in the event any section, sub- VALIDITY section, sentence, clause or p1se of this ordinance shall be declared or adjudged. invalid or unconstitutional, such adjudication or invalidity shall not effect the other o sections, sub-sections, sentences, clauses or phases of this ordinance; providing for the pro- tection under and establishing penalties for the violation thereof as ordained by the City Council of the City of Miami Beach, Florida. 12.01.07 The following basis plumbing principles and ACCEPTED accepted standards are part of this code or STANDARDS plumbing requirements, • 12. 02.01 The art and work of installing in or on PLUMBING buildings in connection, with structures; or on the premises, the pipe, fixtures end other apparatus for bringing in the water and gas supply and for removing liquid and water waste. The said pipe, fixture and apparatus shall include the was supply pipes, the water supply pipes, distributing pipes, the fixtures and fixture traps, the soil, waste and vent pipes, the house drain, with their devices, appurtenances and connections within or directly serving the building or structure, including septic tank connections and house sewer. 12.02.02 The City of Miami Beach Ordinance No. 524 GAS ORDINANCE which is the Gas Ordinance, is a part of this Code. Florida State Hotel Commission gas rules nos. 1452, 1453 and 1454, are also a part of this Code. 12.02.03 Rules and regulations promulgated by -the Florida. GENERAL State Hotel Comniiseion and applicable to the LAWS subject matter of this Chapter shall be and are hereby declared to be a part of this Code. Laws of the State of Florida now existing or hereinafter enacted which are applicable to the subject matter of this Chapter shall be and are hereby declared to be a part of this Code-or amendments. 12.03 01 No person, as principal, agent, manager or EXAMINATION employee, shall conduct, manage or carry on OF the trade, business or calling of a master PLUMBERS plumber, or work as a journeyman plumber, or do any plumbing work of any kind or descrip- tion in the City of Miami Beach, Florida, for which a permit is required, without having first submitted to a written examination, given by the Board of Examiners of Plumbers and obtain- ing from said Board of Examiners a City: of Miami Beach Certificate of Competency. 12.0 .02 The Certificate of Competency shall show that CERTIFICATE the holder of same has sufficient knowledge OF and has had sufficient practical experience t OMPETENCY to do plumbing work. Any master plumber or journeyman plumber, who fails to pass examination, will not be allowed to appear before the Board of Examiners for further examination until the expiration of a period of thirty ( 30) days from the date of such examination. • 12.0 .033 The fee for examination by said Examining Board EXAMINATION of Plumbers shall be Ten (10) Dollars for each FEES master plumber and Five (5) Dollars for each journeyman plumber, for the first examination, payable in advance to the City Clerk of the City of Miami Beach, Florida. 12.03.01- For the purpose of this ordinance, a master MASTER plumber shall be deemed to be the person engaged PLUMBER in or carrying on the business of plumbing or doing the plumbing work; end who has received a Certificate of Competency from the Board. of Examiners of Plumbers of the City of Miami Beech, Florida. 12.03.05 For the purpose of this ordinance, a journeyman JOURNEYMAN plumber shall be deemed to be any person who is PLUMBER employed to do plumbing work for wages or salary and is employed by a master plumber and has been examined and has received a Certificate of Competency by the Board of Examiners of Plumbers of the City of Miami Beach, Florida. 12.03.06 For the purpose of this ordinance, an appren- APPRENTICE tie shall be deemed to be any person doing PLUMBER plumbing work under the direct supervision and in the presence of a certified master plumber or a certified journeyman plumber, and such apprentice is required to have a permit from the said Examining Board of Plumbers to do such plumbing work. 12.03.07 No person shall receive a Certificate of AGE FOR Competency as a master plumber who has not MASTER attained the age of twenty-one ( 21) . PLUMBERS 12.03.08 The Board of Examiners of Plumbers shall DATE OF conduct en examination on or about May 15th EXAMINATION and November 15th of each year to every appli cent for master' s or journeyman' s examination, after filing written application therefor and payment of the fee incident thereto. Every applicant passing such examination to the satisfaction of the Examining Board 'shall receive from said Board of Examiners a Certificate of Competency as a master plumber or journeyman plumber, in accordance with his application; end such Certificate of Compe- tency shall authorize the holder thereof to do plumbing work in the City of Miami Beech until the 31st day of October next succeeding the date thereof. Examination can be called by the City Manager, if necessary, at any time. 12.03.09 All Certificates of Competency issued by the RENEWALS Examining Board of Plumbers shall expire on OF the last day of October of each year, unless CERTIFICATES sooner revoked. Every master or journeyman OF plumber holding a Certificate of Competency COMPETENCY issued by said Board of Examiners of Plumbers, may during the month of October of each year, make application for extension of such Certi- ficate of Competency for en additional year and said Board of Examiners of Plumbers, if satisfied that the holder of such Certificate of Competency is competent to do plumbing work shall grant an extension of such Certificate of Competency for an additional year without examination. No plumber failing to make such application and to obtain such extended Certificates of Competency, during said time, shall- do any plumbing work in the City of Miami Beach, after the expiration of the Certificate of Competency then held, without taking the examination and paying the full fee therein provided for persons originally desiring to do plumbing work in the City of Miami Beach. 12.03.10 A charge of One Dollar ($1.00) shall be made for RENEWAL each renewal, also One Dollar ( $1.00) for a gas FEES fitter and Fifty Cents ($. 50) for a plumber's apprentice. 12.03.11 The Chief Building Inspector shall prepare and REGISTRATION keep a register, showing the name and address OF PLUMBERS of every person, firm or corporation together with .the names of the members of such firm and the officers of such corporation and their addresses, carrying on the business of a merchant plumber of a plumbing business in the City of Miami Beach, showing the name and address of every master plumber, everyjourneyman plumber, and every plumber' s apprentice licensed or permitted to do plumbing in the City of Miami Beach; and shall keep said register up to date by the endorsement of all changes therein and additions thereto. 12.03.12 The Chief Building Inspector of the City of SUPERVISION Miami Beach shall have supervision over the OF installation, alteration, repair and the use of PLUMBING all waste pipes, water, gas, steam, oil pipes and all fixtures in all buildings and other structures or on any lot or premises in the City of Miami Beach 122.0 -.01 Permits shall be obtained from the Building PERMITS Department before any work is commenced or material is placed on the job of installing pipe, pipe fittings, or apparatus for the use of the following systems. 12.04.02 A City of Miami Beach license shall first .be LICENSE obtained before any permit shall be issued on the following installations or• systems. .01 Plumbing .02 Steam .03 Hot Water .04 Solar Systems .05 Septic Tanks .06 Refrigeration .07 Oil Burner Equipment .08 Gas Piping or• Equipment .09 Wells or Pumps .10 Swimming Pools .12 Sprinkler Systems - ! : ' i .13 Ventiletion .14 Ventilation (Kitchens, Dining Rooms) .15 Similar Trades. 12.05. 01 ' No person, as principal, agent, manager or PERMIT employee, shall place or install or cause MUST BE or permit to be placed or installed, any OBTAINED plumbing, steam, hot water, solar system, sprinkling system, fixtures, apparatus and all other plumbing work of any kind whatsoever; or make, or cause or permit to be made any alterations, change in, addition to or repair of any such plumbing, steam, hot water, sprinkling system, oil or ventilating appliances in the City of Miami Beach without first obtaining a written permit for such work from the Building Department of the City of Miami Beach. 10.05.02 Such permit shall be denominated a "Plumbing LOCATION Permit" and shall contain a description of the LOT-BLOCK work to be done thereunder end a statement of SUBDIVISION the location by lot, block, subdivision, street and number sufficient to locate the same, where such work is to be done. 12.05.03 Plumbing permits shall be granted upon written GRANTING OF application therefor to the Building Department. PLUMMBING AND providing applicant has complied with section OTHER PERMITS 12.05.04. 12.05. 04 There shall be plans or drawings, specifications PLANS and details of the contemplated work, when REQUIRtED recuired by the Chief Building Inspector. If the Chief Building Inspector, after investigation, is satisfied that the work desired can be done without violating any of the provisions of this ordinance or any other ordinance or law govern- ing such work in the City of Miami Beach and that the applicant therefor is duly licensed by the City Clerk to do plumbing or other trades aforementioned in the City of Miami Beach, he shall issue a plumbing permit to such applicant, upon payment of the fees therefor. 12.05.05 The issuance of a plumbing permit shall not be PLANS construed as an approval 'by the plumbing APPROVED authority or inspector of the drawings, specifi- cations, plans and details of such contemplated work insofar as the same, or any portion thereof, may be in conflict with the provisions of this ordinance or any other ordinance or law governing such work in the City of Miami Beach. 12.05.06 The holder of a -plumbing permit shell not do or PERMIT perform, or cause or permit to be done or per- VIOLATIONS formed any work other than that designated in such plumbing permit, BASIC PLUMBING PRINCIPLES AND ACCEPTED STANDARDS 12.06.01 The following basic plumbing principles are BASIC hereby a part of this code: PLUMBING. 12.06. 02 All premises intended for human habitation or OCCUPANCY occupancy shall be provided with pipes connect- FOR HUMAN Ed to a supply of pure and wholesome water. HABITATION The water system sell not be connected with unsafe water supplies or cross-connected in any way through plumbing fixtures to the drainage system, or connected to tanks, swimming pools, or other appliances using, storing, or holding any substance other than water from the municipal water supply system supplying pure water. 12.06.03All pipes conveying water to plumbing fixtures FLUSHINshall be of sufficient size to carry water at OF a rate to flush each fixture adequately, without FIXTURES unduly reducing the pressure at other fixtures. 12.06.04 Precaution shall be taken, in the design and SAFETY OF installation of all devices for heating water HOT WATER and storing it in boilers or' hot water tanks, BOILERS, ETC. to avoid danger of exploion, and to prevent back flow of hot water through cold water fix- tures or meters. 12.06.05 Every building intended for human habitation or BUILDING occupancy on premises abutting a street in which SHALL BE there is a public sewer shall have a connection CONNECTED TO with the swwer, and a separate connection for SANITARY each lot or subdivision thereof, if water-closet SEWER or other plumbing fixtures have been or are installed. 12.06. 06 In a building where there is no sewer within (150) BUILDING one hundred and fifty feet, suitable provision SHALL BE shall be made for disposing of the house sewage CONNECTED TO by some method of sewage treatment and disposal SEPTIC TANK or septic tank. 12.06.07 All plubing fixtures shall be made of smooth PLUMBING non-absorbent materials and shall be free from FIXTURES concealed fouling surfaces. SHALL BE NON-ABSORBENT MATE±IALS 12.06.08 The entire drainage system shall be designed and DRAINAGE constructed in a manner which will avoid the SYSTEM deposit of solids, and prevent clogging, and SHALL BE which will quickly conduct rein, storm, or waste DESIGNED water and sewage, to the point of disposal. 12.06.09 Each drainage system shall be so designed and IMPERFECT constructed with such materials as to be proof, MATERIALS for a reasonable life-time of the building, against leakage of water or drainage due to defective materials, imperfect connections, corrosion, settlements, or vibration of the ground or building, temperature changes , or other causes. 12.06.10 Each drainage system shall be provided with en CLEAN OUTS adequate number of cleanouts so arranged that, in case of stoppage, the pipes will be readily accessible through said cleanout. 12.06. 11 Each fixture or combination fixture shell be FIXTURE provided with a separate , accessible, self- TRAP securing, reliable water seal trap, which shall be placed as near the fixture as possible. 12.06.12 Each house drainage syster; shall be so designed TRAP that under conditions of ordinary use there will SIPHONAGE be adequate circulation of air in all pipes in order to avoid the possibility of syphonage, aspiration, or forcing of trap seals. 12.06.13 The soil stack shell extend full size upward VENTS - through the roof and have a free opening; the LOCATION roof terminal shell be so located that there will be no danger of air passing from it to any window or air shaft vent, no clogging of the pipe by articles thrown into it, and so located that roof water cannot drain into it. 12.06.14 Each plumbing system upon completion and before TEST using, shall be tested by means of water or air pressure in the presence of the Plumbing Inspector. 12.06.15 Precautions shall be taken in design and construe- PREVENTIVE tion of plumbing to prevent entrance into the drainage MEASURES system of substances which might clog the pipes, produce explosive mixtures, or destroy the pipes or their joints. 12.116.16 Refrigerators, ice boxes, and other receptacles REFRIGERATORS for storing food, shell be connected indirectly with the drainage system. / 12.06.17 No water-closet shall be located in a room or VENTILATION compartment which is not properly lighted, LIGHT AND and ventilated fyr the access of outer air. AIR 12.06.18 Suitable provisions shall be made to prevent BACK-FLOW sewage from back flowing into a house drainage SEWAGE system. 12.06.19 All plumbing and drainage systems shall be SANITARY maintained in a sanitary condition. MAINTENANCE All plumbing fixtures and rooms where plumbing fixtures ere installed shall be maintained in a sanitary condition. 12.07.01 The minimum waste units for each fixture shall FIXTURE be figured as follows: UNITS Units Branch Vent Water Closet 6 4" 2u or 4" Slop sink integral trap 4 3" 2" or 4" ._ Soda fountain catch basin 4 2" 2" or 4" Urinal trough and stall 2" 2" Laundry trap 4 1b" 2" Sim14 11" 2" Bath tub 2 1*" 2" Shower Head 2 1 -" 2" Lavatory2 la" 2" Dentist Cuspidor 2 ?" 2" Drinking Fountain 1 l " 2" Soda Fountain & Bar sinks 10 4" 2" Safe Wastes 4 2" 2" Sewage ejector -25 gals per min 50 4" 3" Floor Trap 4 4" 2" Sump Pump 6 '-I-" 2" Sand Trap 10 1" 2" t 12.07.02 2 inch pipe Ten (10) Units WASTE PIPE3 II " Thirty-two ( 32) iiUNITS 4 " " One Hundred-sixty (160)_ " CAPACITY 5 " " Three Hundred-eighty (380 " 6 " " Six Hundred-forty (640 , R► 7 H H Twelve Hundred (1200) " 8 " u Eighteen Hundred (1800) " 10 " 't Twenty-eight Hundred ( 2800) 'i 12.07.03 Maximum number of fixture units (as foregoing VENT UNITS equation) permitted on vents: CAPACITY Main Vent 2 Inch Twenty-four ( 24) Units 7 n Eighty (80) 4 n Four Hundred-ten (410) " 3 " Seven Hundred-fifty (750) '� 6 One Th6usand Four Hundred-forty (111- ;0) H 12.08.01 DEFINITIONS OF TERMS 12.08.02 Accepted standards are standards cited in this ACCEPTED code or manuel, or other standards approved by STANDARDS the Chief Building Inspector. 12.08.03 The air gap in a water supply system for plumbing AIR GAP fixtures is the vertical distance between the supply fitting outlet ( spout) andthe highest possible water level in the receptor when flooded. 12.08.011- Approved means accepted as satisfactory to the APPROVED authority having jurisdiction over plumbing. 12,08.05 An area drain is a drain installed to collect AREA DRAIN surface or rain water from an open area. 12.08.06 Alignment is laid to a straight line or given ALIGNMENT angle. 12.08.07 A. S.T.M. is the abbreviation for American A. S.T.M. Society for Testing Materials. 12.08.08 Back flow means the flow of water into a water BACK FLOW supply system from any source except its regular one. Back syphonage is one type of back flow. 12.08.09 A back vent is a branch vent installed primarily BACK VENT for the purpose of protecting fixture traps from self-syphonage. 12.08.10 That part of a piping system other than a main, `BRANCH or to receive fixture outlets not directly connected to the stack. 12.08.11 Branch vent is any pipe connecting from a BRANCH branch of a drainage system to the vent stack. VENT Also note 'Vents-Backl . /1 12.08.12 The building (house) drain is that part of the BUILDING lowest horizontal piping of a building drainage DRAIN system which receives the discharge from soil, • waste and other drainage pipes inside the walls of the building and conveys it to the building (house) sewer beginning five feet outside the inner face of the building wall. 12.08.13 The building drainage system consists of all BUILDING piping provided for carrying waste water, DRAINAGE sewage or other drainage from the building to SYSTEM the street sewer or place of disposal. 12.08.14 The building main is the water supply pipe BUILDING including fittings and accessories, from the water MAIN (street) main or other source of supply to the first branch of the water distributing system. 12.08.15 The building (house) sewer is that part of the BUILDING horizontal piping of a building drainage system SEWER extending from the building main five feet outside of the inner face of the building wall to the street sewer or septic tank, and conveying the drainage of but one building site. 12.08.16 A Building (house) sub-drain is that portion of BUILDING a drainage system which cannot drain by gravity SUB-DRAIN into the building sewer. 12.09.01 A catch basin is a water tight receptacle to CATCH arrest the sediment and prevent its entrance into BASIN the house sewer or drain. 12.09.02 A circuit vent is a group vent extending from in CIRCUIT VENT front of the last fixture connection of a. hori- zontal branch to the vent stack. 12.09.03 A clean-out is a metallic plug which can be removed CLEAN-OUT for the purpose of cleaning or examination of pipe. 12.09.04 A compilation of minimum rules and regulations CODE governing the installation of plumbing, drainage and water supply. 12.09.05 Conductors are pipes located in or outside CONDUCTORS of buildings, conveying storm or rain water from roofs or areas. 12.09.06 Combination fixture is a trade term designating COMBINATION an integral combination of a. sink and one or FIXTURE two laundry trays in one fixture. 12.09.07 Continuous waste and vent is a vent that is CONTINUOUS a continuation of and in a straight line with WASTE AND the drain to whAch it connects - can be VENT vertical or 45 angle. 12.09.08 A continuous waste is a waste from two or more CONTINUOUS fixtures connected to a single trap. WASTE 12.09.09 CROSStSECTION See back-flow or interconnection. 12.09.10 A dead end is that part of a branch of a free DEAD END drainage system which is without a circu- lation of air. 12.09.11 Developed length of a pipe is its length along DEVELOPED the center line of the pipe and fitting. LENGTH 12.09.12 Diameter means the nominal diameter as designated DIAMETER commercially. 12.0 .13 The drain pipe is any pipe which carries water DRAIN or waterborn , waste in a building drainage system. 12.0 .14 A dry vent is any vent that does not carry water DRY VENT or water barn waste. 12.09.15 A dry well is an underground receptacle for DRY WELL disposal of rain water through soil absorption. 12.09.16 A dual vent is a group vent connecting at the DUAL VENT junction of two fixture branches and serving as a back vent for both branches. 12.10. 01 An ejector is a device operated either electri- EJECTORS cally or by water power or other mechanical means so constructed as to elevate liquids from a lower level to a point of discharge into a public or , private sewer or other final means of disposal. 12.10.02 A ferrule is a metallic sleeve used to connect FERRULE lead or iron waste or vent pipe to a soil pipe hub. 12.10.03 A device designed to make connection between FITTING pipes. 12.10.04 A receptacle intended to receive and discharge FIXTURE water, liquids or water carried wastes into a drainage system, A lavatory or wash basin is a fixture designed for the washing of the hands or face. A sink is a shallow fixture ordinarily with a flat bottom and usually used in a kitchen. A slop sink is a deeper fixture than a kitchen sink and is used for the reception of slop. A tray is a fixture used in a laundry for washing clothes. 12.10.05 A fixture drain is the drain from the trap of FIXTURE a fixture to the junction' of the drain with any DRAINS other drain pipe. 12.10.06- A fixture unit is the unit factor chosen that the FIXTURE load-producing values of the different plumbing UNIT fixtures can be expressed approximately as multiples of that factor. 12.10.L07 EVEI, Flood level means level at which waste begins to overflow the top rim of fixture. 12.10.05 For the purpose of this code free circulation FREE CIR- of air is understood to mean a plumbing and CULATION drainage system so designed and installed as OF AIR to keep air within the system in free circula- tion and movement to prevent unequal air pressure of such force as might blow, siphon or affect trap seals, or retard the discharge from plumbing fixtures. 12.10. 29 A public garage is a building which accomodates GARAGES or houses more than three self propelled vehicles. PUBLIC • 12.10.10 A private garage is a building used in /, GARAGES connection with a private residencerhousing self ,, , PRIVATE propelled venicles owned by the occupant of the i>;' residence and used only for personal and family . . service. 12.10. 11 ' The grade or a line of pipe is its slope in GRADE reference to a horizontal plane. In plumping it is usually expressed as the fall in inches per foot length of pipe. 12.10.12 A horizontal branch is a branch drain extending HORIZONTAL laterally from a soil or waste stack Or building BRANOti drain, with or without vertical sections or branches, which receives the drainage from one or more fixture drains and conducts it to the soil or waste stack or to the building (house) drain. 12.10.13 A house drain is that part of the underground H6USE horizontal piping of a drainage system which DRAIN receives the discharge of ell soil, waste and other drainage pipes inside the wills of any building end conveys the same to the house sewer, three to five feet outside the foundation walls of such building. 12.10.14 A house sewer is that part of the horizontal HOUSE piping beginning three feet from the foundation SEWER wall to its connection with the main sewer, or other disposal terminal. 12.11.01 An indirect waste pipe is a waste pipe which does INDIRECT not connect directly with the building drainage WASTES system, but discharges into it through a properly trapped fixture or receptacle. 12.11.0 . Interconnection is any physical connection or INTER— arrangement of pipes between two otherwise separate CONNECTION building water-supply systems whereby water may flow from one system to the other, the direction of flow depending upon the pressure differential between the two systems. 12.11.03 INTERCEPTION See Sand-trap. 12.11.04 Where such connection occurs between the INTER- sources of twp such systems and the first CONNECTION branch from either, whether inside or outside A. S. S. E. the building, the term cross-connection STANDARDS (American Water Works terminology, also American Society Sanitary Engineering) applies and is generally used. 12.11.05 A leader or downspout is the water conductor LEADER from the roof to the storm drain or curb. 12.11.06 1/4 bend - a bend having: the radius of the center LONG line of the bend equal to seven (7) inches plus SylEEP one half the inside diameter of the pipe. 12.11.07 Loop vent is the same as a circuit vent except LOOP VENT that it loops back and connects with a soil or waste - stack vent instead of the vent stack. 12.11.08 An opening constructed to a sewer or any portion MANHOLE of a plumbing system or receptacle and of suffi- cient size to permit a man to gain access thereto. 12.11.09 , See Vent Stack. MAIN VENT 12.11.10 Non-pressure refers to a condition in which a NON- static pressure cannot be imposed safely on the PRESSURE building drain. This condition is sometimes referred to as gravity flow and implies that the sloping pipes are not completely filled. 12.11.11 An offset in a line of piping is a combination OFESET of elbows or bends which brings one section of the pipe out of line with but into line parallel with another section. 12.12.01 Plumbing is the work or business of installing PLUMBING in buildings the pipes, fixtures, and other apparatus for bringing in . the water supply and removing liquid and water borne wastes. Also denote the installed fixtures and piping of a building - see 12. 04.01. 12.12.02 Plumbing fixtures are receptacles which receive PLUMBING and discharge water, liquid, or water borne FIXTURES wastes into a drainage system with which they are connected. 12.12.03 The plumbing system of a building includes the PLUMBING water supply distributing pipes, the fixture SYSTEM and fixture traps, the soil, waste and vent pipes,/ the building (house) drain and building(house) sewer; and the storm-drainage pipes; with their devices, appurtenances, and connection all within or adjacent to the building. 12.12.04 A pool is a water receptacle used for swimming POOL or as a plunge or other bath, designed to accom- modate more than one bather at a time; or a water receptacle designed as a fish pool or flower pool 12.12.05 Pressure drainage refers to a condition in which PRESSURE a static pressure may be imposed safely on the DRAINAGE entrances of sloping building drains through soil, and water stacks connected thereto. 12.12.06 A primary branch of the building (house) drain PRIMARY is the single sloping drain from the base of a BRANCH soil or waste stack to its junction with the main building drain or with another branch thereof. 12.12.07 A privy is an outhouIe or structure used for the PRIVY deposition of human excrement. 12.12.08 Any structure used in whole or in part as a PUBLIC place of resort, assemblage, lodging, trade, BUILDING traffic occupancy or use by the public; or by three or more tenants. 12.12.09 Repairs are defined to consist of fixing leaks REPAIRS and removing obstructions in soil, waste and supply pipes, and to restore defective valves, faucets, and similar appliances to an efficient operating condition. 12.12.10 A relief vent is a branch from the vent stack, RIEF connected to a horizontal branch between the VENT first fixture branch and the soil or waste stack where primary function is to provide for circu- lation of air between the vent stack and the soil or waste stack. 12.12.11 A riser is a water supply pipe which extends RISER vertically one full story or more to convey water to branches or fixtures. 12.12.12 Roughing in is the installation of all soil, ROUGHING waste, vent and water supply pipes within a IN • building. 12.12.13 Rural or isolated buildings are buildings RURAL OR situated at such a distance from a public ISOLATED sewer system that their drainage systems BUILDINGS cannot become tributary thereto. 12.13,01 A pan or other collector placed beneath a pipe SAFING or fixture, to prevent leakage from escaping on to the floor, ceiling or walls. ' 12.13.02 A sand trap or sand interceptor is a water tight SAND TRAP receptacle designed and constructed to intercept OF and prevent the passage of sand or other solids IvTERCEPTOR into the drainage system to which it is directly or indirectly connected. 12.13.03 A sanitary sewer is a sewer designed or used only SANITARY for conveying liquid or water-borne waste from SE"i.R plumbing fixtures, of which all surface and storm water is excluded. 12.13.04 A septic tank is a reservoir or tank, which SEPTIC TANK receives crude sewage, and by bacterial action and sedimentation effects a. process of clari- fication and decomposition of solids. 12.13.05 Sewerage is a sewer or drain intended to receive SEWERAGE domestic sewage- to pumping station or treatment DRAIN works necessary to the collection, treatment, or disposal of sewage. 12.13.06 Note: House Sewage • HOUSE SEWER 12.13.07 A side vent is a vent connection to the drain SIDE pipe through E, 45° wye. VENT 12.13.0g When the word ' shall' is used the rule is mandatory. SHALL - When the word ' should' is used the rule is SHOULD - recommended. MAY The word 'may' implies only permission. 1 2.13.09 Siphonage is a suction created by the flow of SIPHONAGE liquids in pipes. 12.13.10 Back siphonage means the formation of a partial SIPHONAGE vacuum in water supply pipes which may cause a BACK sucking back of polluted water or other liquids into a water supply piping from fixtures. 12.13.11 A slip joint is a connection in which one pipe slips SLIP into another, the joint of which is made tight JOINT with approved gaskets or packing. 12.13,12 A soil pipe is any pipe which conveys the discharge SOIL PIPE of water closets or fixtures having similar functions with or without the discharges from other fixtures. 12.13.13 The end of a pipe or fitting which fits into bell SPIGOT or hub. 12.13.14 Stack is a general term for the vertical main of a STACK system of soil, waste, or vent piping. 12.13.15 A stack vent is the extension of a soil or waste STACK stack above the highest horizontal or fixture VENT branch connected to the stack. 12.13.16 A storm sewer is a sewer used for conveying rain STORM SEWER water or surface water. 12.13.17 A sump is a pit or receptacle at the low point to SUMP which liquid wastes are drained. 12.14.01 A terminal is that part of a drainage or vent system TERMINAL which projects above the roof of the building or at the end of the house drain connecting to the septic tank or house sewer. 1 2.14.02 A trap is a fitting constructed to prevent the TRAPS passage of air or gas through a pipe without materially affecting the flow of sewage or waste water. 12.14.03 A trap crown is where the trap connects to or TRAP becomes a part of the horizontal outlet arm of CROWN the trap which is integral with the trap. 12.14.04 The trap seal is the vertical distance between TRAP the crown weir and the dip of the trap. SEAL 12.14.05 Trap seal depth is indicated by the height of TRAP the water column measured between the overflow SEAL DEPTH and the dip separating the inlet and outlet arms of the trap. 12.1+.06 Trap (deep seal) is a term applied to a trap TRAP - having a water seal twice the depth of the DEEP SEAL common trap. 12.14.07 A trap (drum) consists of a cylinder with its TRAP - axis vertical, the cylinder is larger in diameter DRUM than the inlet or outlet pipe; it is usually four inches in diameter with one and one-half or two inlets and outlets. A trap screw of the same size as the cylinder accessible for cleaning purposes is provided. 12.14.08 A sand trap is a catch basin for the collection TRAP - of sand. SAND 12.15.01 Vent pipe is any pipe provided to ventilate a VENTS drainage or plumbing system of piping. 12.15.02 A back vent is a pipe which connects directly with VENT an individual trap, soil or waste pipe, underneath BACK or back of the fixture it serves and connects to the general vent piping system above this fixture with no part of it below the fixture trap. 12.15.03 A unit vent is one which denotes an installation VENT so arranged that one pipe will serve two traps at UNIT the same point. 12.15.04 A wet vent is that portion of a vent pipe through VENT which liquid wastes flow. WET 12.15.05 A connection between a vent stack and a soil or VENT - waste stack in a manner to prevent minus and plus y®rB pressures in the stacks. Termed also where a vent is vertical or 45° relief vent of the continuous waste and vent type formed by the extension of an upright wye branch or 45° wye-branch inlet of the horizontal branch to the stack. It becomes a dual yoke vent when two horizontal branches are thus vented. 12.15.06 Local vent is a pipe or exhaust conveying foul VENT - air from plumbing fixtures or rooms to the outside LOCAL OR air and not connected to the plumbing system. EXHAUST 12.15.07 A waste pipe is any pipe which receives the WASTE discharge of any fixture except water closets PIPE and conveys the same to the soil pipe or house drain. 12.15.08 The water supply is the water service pipe or WATER supply from the water main or private pumping SUPPLY system to the building served. 12.15.09 The water distribution pipes are those which WATER convey water from the service pipe to the plumbing DISTRIBUTION fixtures. PIPES 12.15.10 Wiped joints is the fusion of metal with solder, WIPED smoothly finished with a wiping cloth, and JOINTS having a thickness of at least 1/4 inch at the point where pipes are joined and at least 1/2 inch in center of joint. 12.15.11 Workmanship is the work of such character that WORKMANSHIP will fully secure the results sought in all the sections of this code. 12.16.01 Every building, hotel, apartment house, stores, OCCUPANCY premises, or other structure for which any BUILDING drainage or plumbing arrangements are constructed MUST BE shall first be inspected and approved by the INSPECTED Chief Building Inspector or deputy before any such building or structure shall be occupied. 12.16.02 City of Miami Beach Ordinance No.193 requires CONNECTION all buildings within one hundred and fifty (150) TO feet of sanitary sewers to be connected to same. SANITARY SEWER 12.16.03 When a sewer is constructed along the street, SEWER avenue or alley adjacent to the property upon VENTS which such building or structure is situated or in close proximity thereto, then such building or structure shall have at least one four-inch house sewer and four-inch vent. 12.16.04 Where two or more buildings are on one lot each VENTS building shall have its own four inch vent and REQUIRED independent four inch sewer_ ., FOR EACH LOT OR PLOT 12.16.05 All sewer pipes within the property line shall be of QUALITY extra heavy cast iron. OF PIPE FOR SEWER 12.16.06 Where house sewer enters City T/C, sewer lateral, HOUBE there shall be a reducing or increasing hub LATERAL installed. No soil pipe shall extend into any City CONNECTION Sanitary sewer laterial; ,offsets shall be made with 4 inch Wyss and 1/8 inch bends with cleanoutrs brougrit to grade level. Note Engineer' s requirement. 12.16.07 No soil, drain, waste or vent pipe shall be built PIPES IN into masonry or concrete walls, columns, beams, or MASONRY footings; suitable chases shall be provided for OR FIRE- them with the approval of the Chief Building Inspector. PROOFING See State rule No. 1412. 12.16.08 In case of a building or other structure being built TERRA COTTA or moved. over an old City T/C sewer, such sewer SEWER shall be relaid with cast iron pipe of the same size UNDER BUILD- as the old sewer or larger size. All T/C sewer in INS any building or other structure shall be replaced or repaired with cast iron pipe. 12.16.09 All house sewer soil or waste pipes or vents r fittings SOIL OR within the property lines or within the building WASTE PIPES or other structures shall be of extra heavy cast iron, WITHIN lead or brass. BUILDINGS 12.16.10 All joints in cast iron waste pipes, whether inside JOINTS or outside of the building line of such buildings IN CAST or structures, shall be made of pig lead one inch IRON deep and oakum thoroughly packed and shall be thoroughly caulked. Paint, putty or varnish is prohibited .from being used. 12.16.11 Horizontal soil pipe shall be installed in as SOIL - direct line from city sewer lateral to extreme end SEER OR outside of building where a clean out shall be HOUSE DRAIN installed above grade, and supported every ten feet. HORIZONTAL Where C. I. trap is used under shower or tub a brass nipple may- be used, on lower floor, to connect to floor drain or on other floors there shall be a two inch Ferrell wiped to a short piece of lead to allow for settlement. 12.16.12 On every change of direction soil line shall be CHANGE IN carried to outside of building with a clean-out. DIRECTION HORIZONTAL 12.16.13 No clean-out shall be installed under any building CLEANOUTS or inside of any room except under sink on the vertical and on vertical stacks servicing more than one bathroom. Plumbing Inspector may request a clean-out placed to the best advantage to clean soil pipes of stoppage. Clean lute shall not be placed in any soil line that cannot be removed and other fixtures added; providing the venting of original fixtures are not interfered with. 1 2.16.14 Connection betweek cast iron soil pipe fittings and CONNECTIONS waste outlets shall be as follows: W.C. shall be BETWEEN connected with a brass ferrell and a piece of lead SOIL AND LEAD at least inches long or to a lead bend wiped with AND FIXTURES round joint. All W.C. floor connections shall be made with brass flange soldered to lead. Baths, showers and urinals shall be connected with a lead trap and brass ferrell or lead stub of at least g inches long wiped with a round joint to brass soldering nipple. 12.16.15 No waste shall enter any lead bend. LEAD BENDS WASTE ENTERING 12.16.16 Drainage pipes or fittings shall not be used when DRAINAGE concealed from view at all times. FITTING 12.16.17 Cellar or basement floor drains shall connect into BASEMENT a cast iron deep seal trap not less than four inches FLOOR by twelve inches so installed with a four-inch clean- DRAINS out before each and every floor drain and vented within fifteen feet from said trap. 12.16.18 May be installed as basement floor drains requirements BAR WASTES but must be directly under fixture served. 12.16.19 Soda fountain wastes may be connected and installed SODA FOUNTAIN as above. WASTES 12.16.20 Hydraulic machinery wastes may be connected and DYDRAULIC installed same as above. MACHINERY L2.16.21 Waste pipes from bubble fountains may discharge BUBBLE into a floor drain or indirect. FOUNTAINS When connected to soil, waste or drain pipes they shall be trapped and vented properly. 12.16.22 Waste pipes from the following shall not connect INDIRECT directly with any building drain, soil or waste OR SAFE pipe. WASTES .01 Refrigerator .02 Ice Box .03 Coffee Urn .04 Glass Water Service .05 Receptacle where food is stored. .06 Receptacle or box where bottled goods are stored in ice. .07 Apparatus using water as a cooling medium. .08 Sterilizer. .09 Water Still .10 Water Treatment Device 12.16.23 Such waste pipes shall in all cases empty into, INDIRECT and above the floor of, an open trapped plumbing WASTE fixture located not more than twenty feet from the LENGTH LIMIT fixture drained, or a sand trap. 12.16.24 Indirect wastes or trap connections shall not be ACCESSIBILITY located in inaccessible or unventilated cellars or other spaoes. 12.16.25 There shall be an air gap of .two inches between AIR GAP safe waste pipes and fixture or flood level. Fixtures or traps shall be water supplied. 12.17.01 Wherever practicable plumbing shall be put in VENTS - on the continuous or wet vent system as follows : WET VENT SYSTEM 12.17.02 The revent shall be taken out of the waste pipe RE-VENT between the stack and the fixture, and as many waste branches, the combined area of which do not exceed the area of said revent, may be con- nected under the same conditions governing the combined wastes and vents, provided that in a sink or urinal waste the revent shall be not less than three inches, but may be reduced to two inches after rising above the sink or urinal; said revent shall then be connected with stack above all fixtures or into a separate vent stack, or be carried through the roof separately. 12.17.03 Each vent pipe shall be connected above the highest VENT OF fixture into the adjacent soil pipe if distance HIGHEST therefrom is not more than five feet. FIXTURE 12.17.04 No vent shall be extended through the roof VENT smaller than two inches. THROUGH ROOF 12.17.05 No brick, sheet metal, earthenware or chimney flue VENTS shall be used as a sewer trap or plumbing fixture WHERE vent. PROHIBITED 12.17.06 No dry vent shall run horizontal more than ten feet. VENTS - DRY . HORIZONTAL 12.17.07 Wet vents can be fifteen feet to the vertical. VENTS - WET HORIZONTAL 12.17.08 Every building or other structure connected to a VENTS FOR sewer or septic tank shall have at least one SEPTIC TANK four-inch vent pipe through the roof. OR SANITARY SEWER 12.17.09 Wye fittings shall be used where vent is taken off the VENT waste line below fixture. CONNECTION 12.17.10 A vent stack or main vent shall be installed VENT with a soil or waste stack wherever relief vents, STACKS back vent, or other branch vents are required in two or more branch intervals. 12.17.11 Each minor fixture trap shall have a protecting VENT TO vent located so that the total fall in the fix- TRAP AND ture drain from trap to went to the vent fitting DISTANCE is not more than one pipe diameter, and the de- veloped length of drain from trap weir to vent fitting is not less than two or more than thirty- six pipe diameters unless special permission is granted. 12.17.12 A back vent or relief vent, preferable in the form VENT - of a continuous waste and vent, shall be installed BACK OR within these limits as may be necessary for com- RELIEF VENT pliance with this requirement. 12.17.13 Fixture drains shall slope continuously from trap VENT - weir and the requirement assuming the fall of 1/4" FIXTURES to the foot, the permissable length of a drain between trap and vents. 12.17.14 Not over six feet for a 1-1/2" drain trap. VENTS - Not over six feet for a 2" drain trap unless MINOR by special permission of the plumbing inspector. FIXTURES 12.17.15 Not over five feet for a major fixture. VENTS - MAJOR FIXTURES 12.17.16 A dual vent for two fixture traps installed as a VENTS vertical continuous waste and vent, or a stack vent DUAL in a dual capacity, may be employed under the following conditions and no additional vents for the trap thus vented shall be required. When both fixture drains connect with a vertical drain or stack at the same level and the developed length and total fall of each fixture drain are within the limits given in section, 12.17.14. 12.17.17 When the two fixture drains connect with the VENTS - vertical drain or stack at different levels, the DUAL FIXTWRE difference in level of the two connections is not greater than five times the diameter of the vertical section of the drain or stack, the diameter of the vertical section or stack is not less than that required for the horizontal drain for both fixtures and the developed length and total fall of each of the two fixture drains is within the limits as -j'"-----, a .40% -x , 11 12.17.15 A lavatory trap and a bath tub or a shower stall VENTS trap may be installed on the same horizontal branch TWO FITTINGS with a back vent for the lavatory trap and with no back vent for the bath tub or shower stall trap, provided the vertical section of the lavatory drain is not less than two (2) inches in diameter and conniocts with the tub or shower drain in a vertical plane, and the developed length of both fixture,. drains are within the aforesaid limits. (12.17.14 Rule) 12.17.19 Two lavatory traps and two bath tub or shower stall VENTS traps may be installed on the same horizontal branch FOUR with a dual vent for the lavatory traps, and with no FIXTURES back vent for the bath tub or shower stall traps, provided that the horizontal branch, except the separate fixture drain, shall be at least two inches in diameter and the fixture drains for the bath tubs or shower stalls connect as closely as practicable upstream from the vent by means of a drainage wye fitting. 12.17.20 Bath room groups, each consisting of a water closet VENTS - lavatory and a shower stall or bath tub, with or without YOKE AND shower head, may be installed on a soil stack with any of RELIEF the following forms of group venting. 12.17. 21 Two bath room groups, or one bath room group and a VENT GROUP kitchen sink and tray combination, may be installed in the highest branch intervals of the soil stack or on a vertical yoke vented branch not less than three inches in diameter with no branch vents other than the yoke vent, provided each fixture drain connects independently to the soil stack or with the water closet drain in the highest branch interval and each fixture drain in all except the highest branch interval connects independently with the yoke vented branch or with the closet drain within the limits. 12.17. 22 One bath room group with group venting in accordance VENTS - with the horizontal branch connected to the soil stack ONE BATH at the same level as the water closet drain, or a ROOM GROUP bath room group and kitchen sink with connections to the stack in the same manner and with group venting in accordance with group vents, may be installed in the same branch interval, of a soil stack within the limits of permissible fixture units for one soil stack and branch interval. 12.17.23 Two bath room groups with group venting or VENT - two bath room group and two kitchen sinks TWO BATH with group ventingin accordance with (group ROOM GROUP venting permitted) may be installed in the same branch interval of a soil stack, provided a relief vent is installed for the second or lower branch intervals from the top group. 12.17.24 In all cases the relief vent required under VENT - aforesaid paragraph 12.17.15 may be a dual RELIEF vent and the size shall be in accordance with CAPACITY sizes of back vents and relief vents. 12.17.25 A group of fixtures in line (battery) on the VENTS - same floor level may be installed on one hori- LOOP OR zontal branch with a circuit or loop vent con- CIRCUIT'' netted to the horizontal branch in front of the last fixture drain, within the limit 12.17.15 provided relief vents connected to the horizontal branch in front of the first fixture drain are installed as follows: 12.17. 26 In each branch interval, if the total fixture VENT - units installed in the branch exceeds one-half BRANCH the number given in Table 12.17. 29 and the INTERVALS number of fixtures on the circuit or loop vented horizontal branch does not exceed two for two inch or three inch horizontal branch or does not exceed one-half the permissible number in column two of first paragraph for a four inch and larger horizontal branches. 12.17.27 A dual relief vent for two circuit or loop VENT - vented horizontal branches in the same branch DUAL interval may be installed. RELIEF 12.17.28 Note Tables 12.17.14, 12.17.15, 12.17. 25. VENTS - LIMITS OF CIRCUIT-LOOP VENTING 12.17. 29 TABLE #1 #2 #3 Diameter of 'Water Closets Fixture Units Other Horizontal Branch Urinals Than Column No.2 ` 2 inches Number 1 Number 12 Il II 2 H 20 H II II 60 H U 16 `r 120 o n U 2L!. rr 180 12.17. 30 Limits for circuit or loop vented horizontal branches VENTS may be increased to one and one-13alf the value given LOOP VENT in above table for three inch and larger branches LIMITS when relief vents are installed so that there is e relief vent inside the first fixture drain, the number of fixtures or fixture units outside the last relief vent does not exceed the limits given in column #2 and #3 of above table, the number of fixture drains between any two successive relief vents does not exceed two for e three inch, three for a four inch, five for a five inch and eight for a six inch or larger branch. 12.17. 31 Two lines of fixtures back to back (double battery) VENT shall not be circuit or loop vented on o/le branch, DOUBLE but each line may be installed on a separate branch BATTERY or circuit or loop vented. 12.17. 32 A group of not more than three fixtures, none of VENT - which discharge greasy wabtes, may be installed on FIXTURES AT a main vent or vent stack below the lowest branch BASE OF vent. STACK 12.17. 33 Main vent stacks shall have e diameter of at least VENT - two inches and in accordance with tha limits of MAIN length and number of fixture units as given in the table below. 12.17. 34 The length of the main vent for application with said table shall be the total developed length as follows: From the lowest connection of the vent system with the soil stack, waste stack, or primary branch to the terminal of the vent, if it terminates separately to the open air. 12.17. 3 VENT TABLES Diameter of? Maximum permissible developed length of vent Soil or Waste Number Vent Stack of . Fixture Units 2" rr 4" II 6" 8" . 2" 24 300 3" 431 80 650 3" 8o 75 600 4 tr 310 3o 240 1000 iI." 620 22 180 750 5" 750 70 320 1000 ii 6" 1440 20 295 20 1000 6" 2880 18 70 180 8" 3100 ! 3o 8o 35o loon 8" 6200 1 25 6o 25o 800 ._ ____. ______ 12.17. 35 Back vents, relief, circuit and loop vents shall be VENT as of above table. TE '`llINALS No vent terminal from the sanitary drainage system _ shall be within twelve feet of any door, window or ventilating opening of the same or an adjacent building unless it is at least three feet higher than the top of such opening, Where roof is occupied as solarium vents must extend seven feet high above roof walk of solarium. 12.,17.36 Extension of vent pipes through roof shall terminate VENT at least one foot above and shall be properly EXTENSION flashed. 12.17. 37 In the event that a structure is built higher than VENT - an existing structure, the owner of the structure HEIGHT TO shall not locate windows within twelve feet of ADJOINING any existing vent terminal on the lower structure, BUILDING unless owner of such higher structure shall defray the expense of, or shall himself make, such altera- tions as are necessary to conform with the provisions of this section. 12.17. 38 The seal of every fixture trap in a plumbing system VENT PRO- shall be adequately protected by a properly installed TECTION TO vent or system of venting, a stack vent, back vent, TRAP SEAL relief vent, duel vent, circuit or loop vent, or a combination. All traps shall be of the same size as the wastes, in sinks, and urinals which shall be l?" . 12.17. 39 No crown vents are allowed. Traps shall have a VENTS - water seal of at least two inches. CROWN 12.17. 40 Where necessary to increase the size of a soil or VENT . vent stack the largest size shall be extended INCREASES throughout and, if a main stack, it shall be taken off the foot of the soil or waste stack and if over forty (40) feet in length carried through the roof independent of the main soil or waste stack, provided that waste stack need not be increased throughout. 12.17.41 Changes in vertical direction may be made by sanitary tees, CHANGE IN short 1/4 bends may be used in drainage lines where VERTICAL the change in direction of flow is from horizontal to DIRECTION vertical. 1 2.18.01 Long sweep bends may be used at foot of stacks where LONG SWEEP where a test tee or wye with cleanout are BENDS installed on the vertical into sweep. 12.18.02 No change in direction greater than 90% in a single CHANGE IN turn shall be made in drainage pipes, same shall be HORIZONTAL made with wyes or 1/8 bends. DIRECTION 12.18.03 No double hub or double tee saddle hub or saddle band PROHIBITED shall be used on soil or vent pipe. No drilling, welding FITTINGS or tapping of soil or waste pipes or the use of wooden plugs driven into soil or waste pipes shall be allowed where holes are drilled for cleaning purposes. 12.18.04 • Double sanitary tees may be used on the vertical stack DOUBLE for waste pipes only. SANITARY TEES 12.18.055 No fixture, device or fitting shall be installed which CROSS CON- will provide a backflow or cross connection between NECTIONS a distributing system of water for drinking or domestic purposes and a drainage system, soil or waste pipes so as to permit or make possible the backflow or cross connection of sewerage or waste water or pool water into a water supply system. 12.18.06 No piping will be allowed in masonry only by PIPING IN permission of the Chief Building Inspector. CONCRETE 12.18.07 No pipes will be allowed vertical in any reinforced PIPES IN concrete beams or columns or fireproofing. CONCRETE 04• 12.18.08 No pipes shall be allowed in grade beams except by PIPES IN special permission of the Chief Building Inspector BEAMS OR when he may allow same at the zero point of beam COLUMNS when same is sleeved during pouring of said grade beams. No cutting or drilling of grade beams will be allowed. 1 2,18.09 Pipes shall not be installed in any foundation or PIPES IN spread footings. They shall be installed above FOUNDATIONS or below all spread footings. OR SPREAD FOOTINGS 12.18.10 Soil pipes from house to septic tanks shall not be DEPTH OF over ten inches below grade at septic tank. PIPE TO SEPTIC TANKS 12.18.11 Material used in any plumbing system or part thereof QUALITY OF shall meet with the accepted standards and the re- MATERIALS quirements of this manual and shall be free from all defects. 12.18.12 Each length of pipe, each fitting, trap, fixture and IDENTIFI- device used in plumbing systems shall be casted, CATION OF stamped or indelibly marked with the maker's mark MATERIALS or name and the weight and quality thereof. 12.18.13 Vitrified clay pipe shall conform to Federal Specifi- VITRIFIED cations for Clay-Sewer Pipe. Joints shall be hot CLAY PIPE poured or cement, and packed with approved packing. 12.18.14 Cast iron soil pipe and fittings shall be as known SOIL PIPE in trade Extra Heavy (XH). GRADE 12.18.15 Wrought iron pipe shall conform with Federal Specifi- WROUGHT cations for wrought iron, welded, black and galvanized. IRON PIPE 12.18.16 Steel pipe shall conform to Federal Specifications for STEEL PIPE steel pipe, seamless, welded, black and zinc coated pipe. 12,18.17 Brass and copper pipe ( I.P. S. ) shall conform to BRASS AND Federal Specifications for brass, seamless, iron COPPER pipe size. PIPE 12.18.18 Brass tubing shall conform to Federal Specifica- BRASS TUBING, tions for land. use. Copper tubing fur use with COPPER TUBING flared or soldered fittings shall conform to SPECIFICATIONS Federal Specifications for tubing, copper, seamless type K.L. and M. copper tubing for use with flanged fittings, or with silver brazed joints - general use I.P. S. Flanged fitting types A - B - C and D. .. 12.18.19 , Lead pipe shall conform to accepted standards and LEAD PIPE shall be what is known to the trade for wastes as REQUIREMENTS D- or XL. 12.18. 20 1*" Pipe weight shall be ?z lbs per fortit. LEAD PIPE 11-11 n if H H 41, H H H SIZES 2 H HH H H 3/4 H II H 4 H H tl H 7-7/ss H II II 12.18. 21 Sheet lead shall not weigh less than 4 lbs per LEAD SHEET square foot. 12.18. 22 Shall be soft ilig lead without solder or antimony LEAD or other foreign substances. CAULKING 12.18. 23 Caulking ferrules shall be of red brass and of the CAULKING following weight and .±mensions; FERRULES 12.18. 24 Size Length Weight SIZES - 2" 1 1 lb. CAULKING 7" 4 1 lb. 12 oz. FERRULES " 4 2 lb. B oz. 12.18. 23 Solderingnipples shell be of red brass - I.P. S. SOLDERING NIPPLES 12.18. 26 Soldering bushings shall be of red. brass - I.P. S. ` SOLDERING BUSHINGS • 12.18. 2 Brass floor flanges shall be of red brass soldered BRASS FLOOR or wiped to lead. FLANGES 12.19.01 All traps shall be effectively vented with an air TRAPS vent pipe of a diameter not less than two ( 2) inches in diameter, provided that a single pipe may be used to vent two traps, through the same fitting when such fitting has effective means to prevent the drainage from one trap entering the other trap and is made of one piece of metal without loose or attached parts, and vent is within the table limits. 12.19.02 Every fixture shall have a separate trap and shall TRAP be placed as close as possible to the fixture they FIXTURES serve and in no case more than eighteen inches from the outlet. 12.19.03 Dentist cuspidors shall be a four inch drum trap TRAPS - and vent shall not be more than ten feet from trap DENTIST CUSPIDORS 12.19.04 All buildings or stores equipped with kitchens TRAPS- where food is prepared for public consumption shall GREASE have a grease trap for each and every sink. 12.19.05 Where there is more than one sink in kitchen or TRAP- pantry, one grease trap may serve as an interceptor INTERCEPTOR for them all, providing all sinks are separately trapped and vented independently. 12.19.06 The main grease trap has to be vented also. The TRAP - size of main grease trap shall be double the com- VENT OF bined capacity of all sinks served. Every kitchen GREASE TRAP shall have at least one door trap, same conuecvea through grease trap or interceptor if possible. 12.19.0? Where sinks are within five (5) feet of grease TRAP - trap they do not have to be retrapped or vented. GREASE FOR All sinks shall have a cleanout exposed just below SINKS the waste of the sink where trap enters the waste line. 12.19.08 If soil pipe to sink is less than five feet and TRAP will rise at a 45o angle just one cleanout on _ GREASE TRAP vertical waste pipe will be required. `tvASTE VENT T19.09 Geese traps shell be installed inside or outside AP of buildings as close to kitchen as possible. GREASE TRAP LOCATION 12.1).10 Greasetreps shall be furnished with a tight fitting TRAP cover the full size of interceptor. Cover shall GREASE TRAP be so designed as to be readily removed and shall REQUIREMENTS have cast in cover the name of the manufacturer and size and flow capacities of trap at 900 efficiency of grease retention. 12.19.11 A suitable socket type wrench for removing and TRAP replacing cover fastening shall be burnished with GREASE each trap. ACCESSORIES 12.19.12 Interior of interceptor shall be designed to pro- TRAP vide a maximum active capacity with a minimum of GREASE distuubance without causing any turbulency or DESIGNS short circuiting. 12.19.13 Interior baffles or partitions shall be so designed TRAP - as to readily permit thorough cleaning of the inter- GREASE ceptor and to permit easy and complete removal of INTERIOR all grease accumulation. 12.19.11- Traps shall be installed in an accessible location. TRAP ACCESSIBILITY 12.19.15 Grease traps shell not have a water jacket. TRAPS - GREASE T RAP WATER JACKET 12.19.16 The following table of various kitchen equipment TRAP - and average efficiency must be certified by the GREASE Iowa Institute of Hydraulics Research Testing Lab- EFFICIENCY oratory or other authority such as the Bureau of Standards, and must comply with War Department Specifications for grease traps. 12.19.17 TRAP GREASE TRAP FEDERAL SPECIFICATION TABLE TABLE Type of ' Interceptor Inlet Outlet , Efficiency Fixture Size Size Size Scullery Sinks T1s Pounds per of Min Grease l - Compartment 20 40 1 1 90% 2 " 25 50 1 1 90% 3 N 4 " 25 50 1 1. 90% 12.19.18 The flow through the interceptor, a cast iron cleanout TRAP-GREASE type control tee shall be installed, a suitable vent CONTROL shall be installed between control fitting and the OF FLOW interceptor. Control tee shall be furnished by the manufacturer of the interceptor. 12.20.01 Oil and gas interceptors shall be installed in all OIL AND gasoline and oil filling stations, public gar es GAS INTER- wash racks, mechanical lifts and in other spaces or CEPTOR buildings where oil or gasoline is dispensed with, WHERE and for washing, greasing and oil changing. REQUIRED 12.20.02 The oil interceptor must be approved heavy duty oil OIL INTER- and gas separator trap with approved retainers and CEPTOR vent. SPECIFICATIONS 12.20.C3 On all wash racks there shall be a sand interceptor SAND INTER- installed in the rack before wash water enters CEPTOR the oil and grease separator trap to sanitary sewer. 12.20.04 All kitchens in hotels, restaurants, or public eating FLOOR DRAINS places shall have cast iron floor drains of four IN (4) inches outlet, and, if possible, connect through KITCHENS grease traps to sanitary sewer; they shall be water supplied above trap for renewal of seal. 12.20.05 All public toilet rooms shall have a two inch floor FLOOR DRAINS drain connected to the drainage system. IN PUBLIC TOILET ROOMS 12.20.06 Cellar drains shall be connected to a sand trap of FLOOR DRAINS 12" x 12° x 12" and a suitable cellar drain pump IN CELLARS to discharge into an open sink that is water supplied and connected to the sanitary sewer. 12.20.07 Plumbing fixtures of all types installed below the CELLAR curb level of the street shall be roughed in FIXTURES- regular, and vented as fixtures above street level REQUIREMENTS must comply with 12.20.08. 12.20.03 All soil or waste shall enter a cast iron or wrought CELLAR iron sealed tank with an approved automatic sewerage FIXTURES - lift attached to a tank. There shall be manholes SEWERAGE for cleaning, and shall comply with 12.20.09 LIFT 12.20.09 Discharge pipes shall rise to ceiling height above CELLAR grade of street and a separate three inch vent FIXTURES - shall be taken off the top of loop and extended DISCHARGE through roof independently of all other vents, FROM TANK and waste discharge into sanitary sewer. OR SUMP VENT 12.20.10 The waste pipe from any refrigerator or other receptacles in which provisions are stored shall not be connected directly with a drain soil pipe or other waste pipe, but shall be arranged to waste into an open sink or sand trap and same connected to sanitary sewer. 12.20.11 The waste pipe for such refrigerator or other WASTE - SIZE receptacle shall not be less than 1* inch pipe, FOR REFRIG- which shall run from an open sink or tray to the ERATOR refrigerator and extend through the roof. Refrigerator traps shall be used. 12.20.12 Soil pipe shall be used under ground. REFRIGER- Galvanized or copper where exposed above ground ATOR with cleanouts at every turn. PIPES 12.21.01 Water closet tanks shall be flushed by a tank of WATER at least four gallons capacity. CLOSETS - TANKS 12.21.02 No water closet bowl equipped with a flushometer WATER valve shall be installed with a side or rear CLOSETS - spud located below the lower part of the flush FLUSHOMETER rim of the bowl. Valve must have an anti-siphon VALVE attachment. 12. 1.03 Latrines, range closets and pedestal urinals shall LATRINES not be installed without the approval of the AND RANGE Chief Building Inspector. CLOSETS 12.21.04 Outside showers and garbage can floor drains shall SHOWERS have a four inch drain with a 12 x 12 x 12 inch cast OUTSIDE iron sand trap. No vent will be required if same is within fifteen feet of any vent stack, measured along pipe to said vent. 12.21.05 Inside showers may have a two inch P trap with a SHOWERS brass nipple when the shower is on the ground floor. INSIDE Upstairs showers shall have a saping pan or sheet lead pan under all shower stalls where a two inch C.I. trap is used there shall be a two inch brass ferrule wiped to a short piece of lead to allow for compression. 12.21.06 Showers in cabanas shall be roughed in regular, SHOWERS IN a trap under each and waste shall be connected with CABANAS the sanitary sewer. 12.21.07 All water closets shall be made of vitreous china- FIXTURES ware. The bowl and trap must be made of the combined EARTHENWARE pattern in one piece . They shall hold a sufficient quantity of water and be of such shape and form that no fecal matter will collect on the surface of the bowl. All water closets shall be equipped with adequate flushing rims so as to flush and scour the bowl properly when discharged. 12.21.08 Range closets may be installed for temporary use only RANGE upon approval of the Chief Building. Tnsneetnr„ 12.21.09 All stall or trough urinals connected to a sewerage URINALS system shall be provided with an effective auto- matic tank and same shall be adjusted so as to cause flushing at regular intervals. Approval only by the Chief Building Inspector. 12.21.10 Bath tubs and all such fixtures, shall be made of BATH TUBS earthenware, vitreous chinaware, enameled iron, or other impervious material. 12.21.11 Same as above SINKS 12.21.12 Same as above or concrete. WASH TRAYS 12.22.01 The connections between fixtures of earthenware, EARTHENWARE vitreous china or enameled iron shall be made by CONNECTIONS means of a brass floor plate not less than 3/16 inc_-:es in thickness, soldered or wiped to lead pipe . The fixture floor flange shall be bolted with solid brass closet bolts. 12.22.02 Floor joints shall be made air tight with an asbestos CLOSET graphite ring; all joints shall be made permanently FLOOR water and air tight. CONNECTIONS • 12.22.03 Plumbing fixtures shall conform to accepted standards QUALITY of the National Bureau of Standards and they shall OF be installed in a manner to afford access for cleaning. FIXTURES 12.22.04 Fixtures other than water closets shall have approved FIXTURE strainers; overflow pipe shall be connected on the ACCESSORIES inlet side of trap and be so arranged that it may be cleaned. 12.22.05 All fixture water supply inleus oz every description FIXTURE shall be located and designed so as to prevent the SUPPLY - possibility of back siphonage or back drainage of any BACK of the fixtures contents into the water supply line. SIPHONAGE Where a water supply inlet cannot be raised above the maximum possible water level, an approved type of vacuum breaker must be installed between the control valve and the fixture in such a manner that no back siphonage is possible under any degree of vacuum. 12. 22.06 Fixture contents against which back siphonage FIXTURE protection is to be maintained includes all CONTENTS pollutional material, sewage, waste water, processing liquids, chemicals and all water and other liquids which can be polluted. 12. 22.07 A cess pool is a hole in the ground with cribbed CESS POOL sides and open bottom into which sewage is PROHIBITED discharged. No such installation will be permitted within the City of Miami Beach. 12.22.08 No exhaust from an engine or blow off from steam PROHIBITED boiler or waste from condensers shall connect CONNECTIONS directly to sewer but shall be an indirect -EXHAUST connection. 12. 22.09 Upon the removal or alteration of any building ALTERATIONS or structure, or the making of any addition thereto; if any new plumbing fixtures are placed therein, either in the original or altered or added portion thereof, such new fixtures shall be properly connected with the plumbing in the original parts of the building or structure; and if the fixtures are to be reset, either in the old or any new part of such building or structure, then both the original and additional fixtures and all altered plumbing shall be made to comply in all respects with the provisions of this ordinance and a permit shall be obtained. 122.22.7.0 All hangers and pipe supports shall be securely HANGERS made. No wooden plugs into masonry shall be allowed. 12. 22.11 All stacks shall be provided with floor rests HANGERS OR at ten foot intervals on each floor. STACK Horizontal piping shall be supported at intervals SUPPORTS not to exceed ten feet; cast iron soil every five feet. 12. 22.12 Pipe supports shall be made of heavy iron posts, PIPE wall hangers or brackets, concrete or masonry SUPPORTS piers. 12. 22.13 The joint at the roof shall be made water tight ROOF by the use of copper, lead-galvanized sheet FLASHING metal. • 12. 22.14 All roof drains shall be connected to storm sewer ROOF DRAIN or street inlet and such drain shall be placed under `OR the sidewalk and shall not be smaller than a four RAIN LEADERS inch cast iron pipe to gutter. .02 Surface or Seepage Water: No opening shall be allowed in the sewer pipes of any building for the purpose of receiving the surface or ground water of a cellar, basement or area. 12. 22.15 All excavations required for the installation of a DRAINAGE building or other drainage system, or any part thereof, EXCAVATION within the walls of such building or outside of the building to lot line, shall be open trench work and all such trenches shall be kept open until the pipe therein shall have been inspected. 12. 22. 16 No tunnelling for drainage under pavements, side- DRAINAGE walks or driveways will be allowed. TUNNELLING 12. 22.17 All concealed lead work shall be made proof against RAT PROOFING damage by rats by a covering of galvanized wire cloth securely fastened in place. 12. 23.01 Every service pipe from a city main tap to any WATER building or other structure or sprinkling system, SERVICE yard hydrants or appliance shell be not less than ..IPE three-fourths of an inch in internal diameter. 12. 2-2.02 The City Water Department in every instance reserves WATER DEPART- the right to, at its own option, designate and pre- MENT RULES scribe the size of a service connection, either upon original installation of a new connection or upon any renewal or-'.teplacement of any old connec- tion and in any case where a size of service other than that applied for by the tenant, or previously existing, is designated and prescribed by the City, the tenant shall be bound thereby. 12. 23.03 No one but an authorized employee of the Water CITY CURB Department is allowed to touch any water main, COCKS service pipe, meter, stop-cock, curb-cock, or other fixture belonging to or under the control of the city. 12.23.04 Any plumber finding repairs or changes necessary NOTICE TO will shut off the water at the stop-cock at the WATER building. In case it is necessary to shut off DEPARTMENT the water at the curb he will notify the Water Department before he does. 12123.05 Water supply materials shall be of brass, copper, WATER cast iron, wrought iron, galvanized or steel gal- SUPPLY vanized and all fittings shall be of the same MATERIALS material. 12.23.06 In all premises where steam boilers, hot water RELIEF boilers or tanks or solar water heater systems VALVES that are supplied with water from the City Water Department or mains and connected to same, the owner and plumber must install an approved relief valve. 12.23.07 A pressure valve, vacuum and a temperature relief PRESSURE valve shall be installed to prevent damage from VALVE collapse of boiler or water tank or solar water TEMPERATURE systems. VALVE 12.23.08 Check valves shall be so located that there is no CHECK shut off or check valve between the tank and VALVES relief valve. 12.23.09 In all cases where pipes are connected direct with WATER boilers, water heaters, water tanks and similar METER fixtures, protection to City water meters shall PROTECTION be observed so that hot water shall not back up into city water meter. 12.23.10 The owner will be held responsible for the cost OWNER' S of labor and material to repair said meters when RESPONSIBILITY repairs are necessary due to backing up of hot water FOR WATER through supply pipes. METERS 12.23.11 The size of water pipe shall refer to the nominal SIZE OF internal diameter and shall vary with the number of WATER PIPES fixtures supplied thereby as follows: for nipples TO FIXTURES and tubing only, not less than three-eighths of an inch (3/8") ; toilet and lavatory supplies for not more than three fixtures, not less than one-half (1/2") ; for not more than twenty-four fixtures, not less than three-quarters of an inch (3/4") ; for not more bnan rorty (40) fixtures, not less than one (1) inch; for not more than eighty (80) fixtures not less than one and one-quarter inches ( 1-1/40) ; for not more than one hundred and fifty (150) fixtures, not less than one and one-half inches (1-1/20) ; for not more than three hundred (300) fixtures, two inches (2") ; for every additional one hundred and fifty (150) fixtures add one-half an inch (1/2") additional. 12.23.12 On all water pipe lines supplying water to any STOP ON plumbing system, fire-line, sprinkler, or other SUPPLY water supply system there shall be a separate LINES stop-cock on each and every pipe line in a con- venient and accessible place, outside of the building and independent of city service stop-cock, which shall be used by the Plumber or whoever desires to turn off the water. 12.23.13 In apartments, hotels and rooming houses every bath STOP IN room shall have a stop-cock on each supply to each APARTMENTS- fixture and in an accessible place. HCTELS,ETC. Note State Rule No. 1411. 12.23.14 Flushometers or similar connections shall have a FLUSHOMETER vacuum breaker to prevent back siphonage. VALVES 12.23.15 Water closet tanks shall have a valve accessible WATER CLOSET below said tank. TANK STOP 12.24.01 Any person, as principal, agent, manager, or employee PENAL COST commencing or doing any plumbing work for which a FOR DOING plumbing permit is required, without first obtain- WORK WITHOUT ing a plumbing permit therefor, shall pay double PERMIT the fee therein provided for a plumbing permit authorizing such work, and subject to Penalty for Violation 12.34.14. Note 12.05.03. 12.25.01 A double fee shall not be charged in cases of , EMERGENCY emergency work necessary to be done in order to WORK prevent material injury or damage to property and provided that the issuance of a permit upon payment of such double fee shall not be a defense to a prosecution for a violation of any of the provisions of this Ordinance. 12.25.02 All plumbing work done shall be subject to inspec-- INSPECTION tion and a written notice shall be given to the NOTICE Chief Building Inspector by the master plumber, firm or corporation doing such plumbing work or having same done, as soon as the work is ready for inspection. Such notices shall be given for inspection of both the rough and finished work. The person, firm or corporation doing such plumb— ing work shall secure a certificate from the Plumbing Inspector, showing the result of such inspection and shall deliver the said certificate to the owner of the premises on which the same is done, or to the authorized representative of such owner. 12.25.03 Floors shall be left up in all bathrooms and WORK LEFT elsewhere above all plumbing until the plumbing UNCOVERED pipes and other plumbing work shall have been examined, tested and approved by the Plumbing authority or inspector. 12.25.04 Inspection of plumbing shall be made within forty— TIME FOR eight (48) hours after a notice that the same is INSPECTION ready for inspection shall have been received by the Building Department on a written duplicate application blank furnished by said Building Depart— ment. 12.25.05 The master plumber or 3 oirneyman plumber shall TESTS OF apply the water test on all new plumbing work for ROUGHING the approval of the Chief Building Inspector or his deputy in his presence. Test shall comply with State Rule No.1408. 12.25.06 Before fixtures are placed in connection with the ROUGH TEST plumbing of any building or structure and before any portion of the drainage system of any building or structure is covered or concealed from view, the outlet from the soil pipe and all openings therein below the top shall be hermetically sealed and the pipe shall then be filled with water to the highest point in the system. Soil pipes and fittings shown to be defective shall be removed and replaced with sound pipes and fittings. 12.25,0? Every part of the work shall successfully stand TESTS SHALL such tests for one (1) hour and shall in all BE APPROVED respects conform to the requirements of this ordinance to the satisfaction of the Chief Build- ing Inspector or his deputy. 1.2.25.08 Every person, firm or corporation doing any plumb- DEFECTIVE ing work shall immediately remove and replace any MATERIAL and all defective material, waste pipe, soil pipe or drainage pipe and any and all defective work, when required so to do by the Chief Building Inspector or his deputy. 12.25.09 Any water closet, urinal, sink or other fixture DEFECTIVE set up, used or installed otherwise than in FIXTURES accordance with this ordinance, or any other ordinance or law governing such work in the City of Miami Beach, or which may become defective, dangerous or in any way unfit for service, shall upon notice, either verbal or in writing, from the Chief Building Inspector, remove or repair same to his satisfaction. 12.25.10 Notice shall be given by the Chief Building Inspector NCTICE BY or his deputy to remove or repair any defective CHIEF material and same shall be made to comply with the BUILDING provisions of this ordinance and of every other INSPECTOR ordinance and law governing such work in the City of Miami Beach, within the time fixed in such notice or within any extension thereof granted by the Chief Building Inspector or his deputy. 12.25.11 No person shall occupy or make use of any hotel, OCCUPANCY apartment house, rooming house, store or building or other structure in which plumbing has been installed or constructed, until after the Chief Building Inspector or his deputy shall have issued a final certificate of approval of the plumbing work therein or in con- nection therewith. Certificate of Occupancy shall be issued as per the zoning regulations from the Building Department. 12.25.12 No soil or drainage pipes shall pass over any water PROTECTION supply tanks, reservoirs or other receptacles holding TO MATER water supplies either hot or cold. TANKS 12. 25.13 No water pipe, soil or drainage pipes shell be PROTECTION installed over any electrical machinery or equip- TO ment. LEC 'RI C AL MACHINERY ' 12. 25.14 No plumbing pipes, soil waste or supply shell be TRANSFORMER installed in eny transformer room. ROOMS 12. 25.15 No overflow pipes from cisterns, supply tanks, OVERFLOW expansion tanks, or dtip pans shall connect PIPE direct with any drainage system but shall be connected as an indirect installation. 12. 25.16 No material other then specified in this code shall ALTERNATE be used, unless accepted and approved by the Board MATERIAL of Examiners for Plumbers or by the Chief Building Inspector•. 12. 26.01 No privy vault shall be dug or constructed in the PRIVY City of Miami Beach except that the Chief Building VAULTS Inspector may permit such vaults to be dug or con- PROHIBITED structed for temporary use only and shell specify in the permit the length of time during which same may be used. 12. 26.02 It shall be unlawful for any person to maintain PRIVY such privy vault a longer time then specified. in VAULT such permit. PERMITS 12.26.03 Such vaults shell be maintained in a sanitary con- PRIVY VAULT dition during use. MAINTENANCE 12.26.04 In case any plumbing is required or desired in the BUILDING construction, alteration or repair of any building PERMIT or structure requiring a building permit, no BEFORE plumbing permit shall be issued until after the PLUMBING building permit for such building or structure PERMIT shell have been previously issued. 12.26.05 No plumbing permit shall be issued for repairing PERMIT leaks in drain, soil, waste or vent, but work NOT must be performed by a licensed plumber. REQUIRED 12.26.06 Should any trap, drain, soil, pipe, waste or vent REPAIR pipes become so defective as to require removal PERMIT or replacement with new material, in whole or in REQUIRED part, or should any toilet, wash basin, laundry, tray, sink, slop sink, slop hopper or any other fixture be taken up or reset, or be replaced with a new fixture, a plumbing permit must first be pro— cured therefor, and a licensed plumber shall do the work. 12.26.07 No person, as principal, agent, manager or employee, SEPTIC shall install or repair or cause or permit to be TANK installed or repaired any septic tank within the PERMITS City of Miami Beach without first having obtained from the Chief Building Inspector a permit for such repair or installation. 12.26.08 The Florida State Board of Health requirements shall SEPTIC be complied with regard to size and construction TANK of septic tanks and drain fields. REQUIREMENTS 12.26.09 When any building or other structure, in or for SEWER which any drainage or plumbing arrangements are con— CONNECTIONS structed, is not situated within 150 feet of a REQUIRED sanitary sewer, so as to require connection to the sanitary sewer, then such drainage or plumbing arrange— ments shall be connected with a septic tank. 12.26.10 Septic tanks shall not be located less than five SEPTIC feet from any property line or less than ten feet TANK from any dwelling; except when it is impossible LOCATION to maintain these distances, then the Chief Building Inspector may issue a permit for a septic tank at a less distance from property lines and dwellings, provided the same shall not be detrimental to health or unsanitary or endanger the structural footing or building. 12.26.11 On all lots where buildings are to be constructed TEMPORARY there shall be temporary toilets installed and TOILET connected to sewer or septic tank before work on FOR the building is started. NEW BUILDING 12.27.01 There shall be one lavatory and one water closet STORES - for each individual store. REQUIREMENTS iz.47.02 There shall be one water closet, one lavatory, SINGLE-FAMILY one shower or tub and one sink for each and REQUIREMENTS every family. 12.27.03 There shall be one water closet, one lavatory, DUPLEX one shower or tub and one sink for each and REQUIREMENTS every family. 12.27.04 Same requirements as for single-family and APARTMENT duplex. HOUSES - See State Rule No. 1405 for requirements. REQUIREMENTS 12.27.05 There shall be at least one water closet, one HOTEL -- lavatory, and one tub or shower for every two SANITARY sleeping rooms, same shall be installed be- REQUIREMENTS tween the sleeping rooms and be accessible from each room without entering any public hallway. See State Rule No. 1404. 12.27.05 The same requirements as for hotels shall be in ROOMING force . HOUSE See State Rule No. 1406. REQUIREMENTS 12.27.07 The same requirements as for hotels shall be BOARDING in force. HOUSE REQUIREMENTS 12.27.08 There shall be one water closet and one lavatory RESTAURANTS- for each sex in restaurants of five to twenty REQUIREMENTS seating capacity. Also all other requirements of the State Board of Health shall be complied with. See State Rule No. 1407. 12.27.09 A soft drink stand is a place where soft drinks SOFT or fruit juices are served. No beer or sand- DRINK wiches shall be served. There shall be one water STANDS closet and one lavatory; a floor drain and a sink near where the soft drinks or juice is served and all boxes holding iced soft drinks must comply with the health laws and be drained to sand trap. 12. 27.10 No work on a plumbing or other system which conflicts CONFLICT with any of the basic principles stated herein shall WITH be accepted or approved by the Plumbing Inspector, PRINCIPLES and only work on a plumbing system that is in accord- ance with such basic principles shall be accepted or approved. 12. 28.01 - There shall be charged and collected by the City Clerk, FEES FOR on certification by the plumbing inspector en inspec- *PLUMBING tion fee of fifty cents (500) for each fixture in new PERMITS and reconstructed plumbing work with a- minimum permit of one dollar ($1.00) before the issuance of any permit, which said fee shall be placed to the credit of the General Fund of the City of Miami Beach. 12. 28.02 The fees for septic tank installation or repairs shall FEES FOR be a minimum of one dollar ($1.00) for any permit; SEPTIC TANK a 500 gallon installation 01.00 and for a one thousand INSTALLATION gallon installation, 42.00; and ;'1.00 for every one thousand gallon or part thereof over the first thousand gallons. 12. 2& 03 42.00 for every $1,000.00 contract or portion thereof. FEES FOR STEAM HEATING 12.28.04 :12. 00 for every $1,000.00 contract or portion thereof. FEES FOR HOT WATER HEATING 12.28.05 4'2. 00 for every $1,000.00 oontract or portion thereof. FEES FOR SOLAR WATER HEATING 12. 28.0'6 42.00 for every $1,000.00 contract or portion thereof. FEES FOR REFRIGERATION 12. 28.0 42. 00 for ever FEES FOR every 1,000.00 contract or portion thereof. OIL BURNERS 12. 28.06 _ $2. 00 for every $1,000.00 contractor portion thereof. FEES FOR WELLS 12.28.0 9 y�r_.00 for every 11,000.00 contract or portion thereof. FEES FOR SWIMMING POOLS 12.20.10A for every §1,000.00 contract or portion thereof. FEES FOR sPR INKLER SYSTEM; 12. 28.11 X2.00 for every „'1,000.00 contract of portion thereof. FEES FOR VENTILATION 17. 28.13 The plumbing inspector shall keep, in proper books PERMIT - - for that purpose, a true and correct account of all 41ECORDS plumbing fees received, the name of the person paying same, the date and the amount of each payment. • 12. 22.01 The word or term "solar°° is herein used to indicate SOLAh WATER all heaters used for gathering heat from the sun HEATER for the purpose of heating water. 12. 2;.02 There shall be a license required of all, solar water SOLAR WATER heating contractors. A master plumber may do this HEATING work. CONTRACTOR1S LICENSE 12.25.03 • Each solar heater or any part thereof shall be con- SOLAR WATER sidered as a plumbing fixture fdr the purpose of this HEATER Code. DEFINITION 12. 2 .04 No such solar water heater shell be erected, constructed, SOLAR built, placed or repaired, in the City of Miami Beach ERECTION which does not conform to the requirements of this Code and the Miami Beach Building Cope. 12.25.05 A coil box shall be made of not less than twenty-four COIL ( 2L ) gauge galvanized iron or other material having BOXES equal strength and rust and decay-resisting qualities and shall be constructed and supported so that no sag will develop in the side and rails when supported. 12.29.06 Solar water heaters shall be anchored to supports of SOLAR at least one and one-quarter inch by one and one-quarter SUPPORTS inch by one-eighth -inch , (li x 1$ x i/o" ) galvanized angle iron, or other material equal ' in strength end rust end decay-resisting qualities. These supports shall be fastened to e galvanized metal floor plate to be anchored to the roof rafters with hot tempered galvanized jay bolts not less' than three-eights of an inch (3/ ) in diameter. 12. 29.07 Tanks shall be galvanized inside and outside or SOLAR HEATER shall be of some other corrosion resisting TANKS ; HALL material, designed to operate under not less HE GALVANIZED than one hundred (100) pound pressure, and shall be tested to 150 hydrostatic pressure. 12. 29.0] Floor plates end uprights shall be of galvanized ,SOLAR FLOOR angle iron and of a size not less than one and PLATES one-half (i1-) inches by one and one-half (11-) inches by one-eighth (1/s) inch or of some other material and shape having equal strength and rust, fire and decay-resisting qualities; all other supports and traces shall be of material having similar qualities and strength. 12.29.09 Tank box base to support tank shall be bolted or SOLAR TANK attached to the metal tank frame in an approved BOX BASE manner. Tank box base, if made of wood, shall be constructed of at least four (4) pieces of two-by-four (2X4) inches nominal size timber, covered with at least one inch (1'" ) nominal size stock; or, if made of other material must be rust-resisting and of at least equal strength. 12. 29.10 All insulation around the tank shall be et least SOLAR TANK five (5) inches of ground, regranulated cork or its INSULATION , . equivalent, tamped in the tank box in such manner as not to lose more than •one degree of heat per hour from the tank. 12. 2 .11 The tank bQx must extend five (j) inches above SOLAR TANK the tank and down each side to .a. point et least BOX to the top of the metal tank supports, end shell CONSTRUCTION be securely fastened to the two-by-six (2X6) inch timber forming the tank brace. Where not otherwise protected, the tank box shell be completely covered with galvanized iron lath and cement plaster, or twenty-four (24) gauge galvanized iron lath end cement plaster, or twenty-four (24) gauge galvanized iron, or sixteen (16) ounce copper, or other approved covering. This type of construction will be allowed in residences only; in all other types of construction the enclosure shall be fireproof. 12. 29.12 When necessary to repair existing wooden systems, REPAIRS - they shall be replaced with systems meeting, the REPLACEMENTS requirements of this Code. 12. 20.13 Hot and cold water supply pipes for such tanks SUPPLY shall be installed by plumbers to 2_ point above INSTALLAt the ceiling joist end adjacent to location of TION the tank box. Connections between the tank and the heating elements and between the tank end hot and cold water supply lines, shell be made as one installation under the provisions of this RELIEF . Code. A relief valve, pressure or vacuum valve, VALVES and temperature valve shall be installed on every insulation. 12. 30.01 The work of installing in or on a building or STEAM structure or on the premises, boilers, piping, HEATING fixtures or apparatus for the use or generating . or conveyance of steam to radiators, pressers, engines or any similar appliances. 12.30.02 A licensedmaster plumber or a licensed journeyman STEAM plumber under a master plumber may do this work FITTING providing a permit is taken out and inspection LICENSE requested. 12. 0.03 A master pipe fitter or journeyman pipe fitter .may MASTER also do his type of work providing he has passed PIPE-FITTER examination by the Plumbing Board of Examiners and has paid the license fee and taken out a permit for each job or install tion or reinstallation. 12.30.04 Hot water heating boilers in ell premises where STEAM steam boilers or hot water boilers are supplied BOILERS with water from the City of Miami Beach Water supply, the owner must see that a suitable safety valve, vacuum, air or other relief valve or device is placed thereon to prevent damage from collapse under heavy pressure from explosion if water is shut off. 12.30.05 In all cases where pipes are connected direct with CHECK boilers, feed water heaters, or other fixtures VALVES where pressure is or can be generated, there must be a check-valve placed in the pipe between such fixture and the meter. 12.30.06 Where the above is not done the consumer or plumber RESPONSI- will be held responsible for any damage to meter or SILITY other fixture on the service pipe and for cost of labor in repair. 12.30.07 Boilers shall have a reducing pressure valve according REDUCING to boiler rating as specified.. on name plate. PRESSURE - VALVE 12. 30.08 - No blow-off shall be connected direct to any BLOW-OFF sewer or drainage system but may be connected to deep seal sand trap. 12. 30.09 Water column try cocks, ejectors, pressure gauge WATER and safety valves must be kept in perfect working COLUMN order and. repair. 12. 30.10 Boilers shall not be fixed to produce a pressure SAFETY VALVE greeter than the safety valve is set. ON PRESSURE BOILERS 12030.11 A high pressure boiler is any boiler r,here over 15 HIGH-PRESSURE pounds steam pressure is generated. BOILERS 12. 30.12 A low pressure boiler is any boiler generating LOW-PRESSURE below 15 pounds pressure. BOILERS 12, 30.13 High pressure boilers shall be inspected by the BOILER boiler inspector of en insurance company and reports INSPECTION of said inspection must be filed with the Building Department. No high pressure boiler shall be used without said inspection. 12.31.01 Master plumbers, master pipe fitters or oil burning OIL BURNER companies must have a City of Miami Beach license CONTRACTOR' S and must take out: permit and furnish a plan • LICENSE describing the work contemplated. 12. 31.02 Inspection and approval by the Fire Department OIL BURNER and the Building Department is necessary. INSPECTION 12. 31.03 Oil burner or steam fitting companies shall not OIL BURNER install water supplies or do any drainage or SYSTEMS electrical work; they shall employ a master plumber or a master electrician to bring service and supplies and waste within five feet of the appliance. 12. 32.01 The regulations of the State Board of Health are SWIMMING a part of this code. POOLS 12. 32.02 A license and permit must be secured before work SWIMMING is started and a complete plan, approved by the POOL State Board of Health, showing supply and waste CONTRACTORS outlets indicated thereon; also pumps, chlorina- tions,etc. Master plumbers or general contractors may install this work on their license of their respective trades. 12. 32.03 All supplies and drainages shall be installed by S,wIMMING a master plumber. Concrete and appliances may POOL be installed by a swimming pool contractor and DRAINAGE electrical work must be done by a licensed master electrician. 12.32.04 Swimming pools shall be constructed in accordance SWIMMING with United States Public Health Service Bulletin POOL No. 139 and the Board of Health of the State of REGULATIONS Florida. 12.32.05 Under no circumstances shall piping systems be so SWIMMING designed or installed as to permit pool water POOL to enter a portable water supply system, nor CROSS - waste water or sewerage to enter pool through 'CONNECTIONS backflow or interconnections. 12. 32.06 Supply from portable water system shall be fed SWIMMING indirect through an elevated tank with an air POOL break between city water supply and water supply WATER to pool or by a well. SUPPLIES 12. 32.07 Where filters are installed and filter washing SWIMMING with the recirculation pump is not possible, a POOL washwater pump of proper capacity shall be in- FILTERS stalled and a suction well or small elevated tank used to supply water to the pumps, the discharge being above the flow lines. 12. 32.08 No pool drain or drains from the filters, where the SWIMMING recirculating system is used, should be directly POOL DRAINS connected to sewers. Such drains should discharge by an indirect connection to a properly trapped sump. 12. 32.09 Baptistries, ornamental and lily ponds, aquariums, BAPTISTRIES ornamental fountains, basins and similar appur- LILY PONDS tenances shall have supplies thereto protected from back flow. 12.33.01 Ventilation as applied to plumbing, bathroom, VENTILATION kitchen and dining rooms and the work of installing within premises or buildings, the pipe fixtures or other apparatus for the removal of air or odors. 12.33.02 Ventilation contractors shall have a City of Miami VENTILATION Beach license and a permit to install pipes and CONTRACTOR'S appliances shall be required. LICENSE 12.33.03 The ventilation permit fees shall be based upon VENTILATION building permit fee regulations. FEES 12.33.04 A plan shall be furnished showing the size of ducts VENTILATION and appliances. Galvanized ducts shall not be PLANS smaller than twenty—four (24) gauge galvanized. 12.33.05 Bathroom ventilating ducts shall start at the grill VENTILATION in the bathroom and it shall be continuous and OF BATH reasonably tight. It shall be continuous through ROOMS the roof and. no other openings entering this duct except ventilation of bath room. 12..S0.06 No flue or opening from any kitchen wnere meals VENTILATION are prepared or served shall open into any street, KITCHENS alley or areaway without being completely enclosed in galvanized duct from grill or opening and this duct to terminate above the roof and not to be within fifteen (15) feet of any window or directly under a window. No electric ventilating fan or exhaust fan shall discharge into a street or alley but shall discharge into a duct that discharges above the roof of the building. 12.33.07 Kitchen hoods and the ventilation of kitchens should VENTILATION be connected to a ventilating flue of brick when KITCHEN building is constructed. Galvanized vent flues will HOODS be allowed with consent of the Building Inspector if no fire hazard is thereby created. 12.33.08 Gas appliances shall be ventilated through transit or VENTILATION soil pipe that are insulated 2" from any wood, and OF GAS shall not be connected to any other flue or ventilating APPLIANCES duct but shall be installed independently of other ducts. 12.34.01 No galvanized pipe or vent flues shall enter any VENT FLUES - space between ceiling and roof without being con- PIPE BETWEEN tinuous from grill face through the space or attic CEILING AND and through the roof and shall have another pipe ROOF outside of same which shall act as a fire retardant. Also all vent ducts shall have a return hood thereon subject to the Building Inspector' s approval. 12.34.02 Where a building or structure has been inspected CONDEMNA- and the plumbing work (or work of other trades) TIONS has been condemned by the Chief Building Inspector as being in an unsanitary condition or defective Rule 12.34.03 shall apply. 12.34.03 A condemnation notice shall be given in writing by CONDEMNA- the Chief Building Inspector to the owner, agent TION NOTICE or occupant of the building or structure condemned and in such notice he shall designate the repairs or improvements required to be made. 12.34.04 If the owner, agent or occupant objects to such OWNER'S condemnation or to the making of such repairs or APPEAL improvements, he may within three days after such notice appeal to the City Council from the decision of the Chief Building Inspector. Such appeal shall be taken by filing a notice, in writing, with the City Clerk and a copy with the Chief Building Inspector stating the objections to such condemnations or to such repairs or improvements and, a statement that he appeals to the City ®ouncil for relief. 12.34.05 If an appeal is so taken by such owner, agent or APPEAL TO occupant, the same shall be presented for hearing COUNCIL at the next regular meeting of the City Council provided notice of the time to which such hearing is continued shall be given to such owner, agent or occupant, and the City Council may hear evidence and argument touching the issue and may affirm, reverse or modify the order of the Chief Building Inspector and the decision of the City Council on such an appeal shall .bg. final and conclusive. 12.34.06 When plumbing in any building has been condemned as UNSANITARY unsanitary and no appeal taken as herein provided, PLUMBING or if taken and the order of the Chief Building Inspector is affirmed or modified. 12. 3' 07 The owner, agent or occupant shell immediately OWNER make such repairs and improvements as may be SHALL recuired by the City Council end unless the dame ;00MPLY shall be commenced within three days after notice of the decision of the said City Council, it shell be the duty of the Chief Building Inspector to - post at some conspicuous place on such building or structure one or more notices, which shall be substantially in the following form: 12. 34.08 " WARNING" °iARNING "This building (or structure) has been condemned as unsanitary and unfit for human habitation or occupancy and it is unlawful for any person to live in or use the same. By order of the City Council. Chief Building Inspector. " 12. 34.O9 Such notice may be in typewriting end shell remain NOTICES on such building or structure until the repairs or improvements shall have been made and. the same shall then be removed by the Chief building Inspector, or by such person as may be authorized by such official to do so. 12. 34.10 It shall be unlawful for any person to remove or REMOVAL ZOVAL deface same. After building or structure has OF been placarded on account of unfit plumbing and NOTIC: S until the repairs or improvements recuired shall have been Wade. ' 12.34.11 It shall be unlawful for any person to live in or OCCUPANCY occupy such building or structure, whether for NOT business or residence purposes, or to rent, let ALLOWED or hire the same or any part thereof, or to collect, receive or pay any rent therefor, whether as agent, owner, tenant, or otherwise. 12. 34.1 very person, firm or corporation doing business as REGISTRMTION a merbhant plumber (or other trades) in the City DISPLAY of Miami Beach shall, at the place of such business, display a business sign showing the full registered name of such person, firm or corporation; end it shall be unlawful for any person, firm or corooretion not so res:istered'to do business plumbing i�orhy f Miatni therein. beach, or to advertise to do an "3 SECTION 2. 'That this Ordinance shall go into effect immediately upon its passage and posting as required by law. PASSED and ADOPTED this 28th day of June, A. D. 1944. Mayor Attest : y C erk 1st reading - June 8, 1944 2nd reading - June 8, 1944 3rd reading - June 28, 1944 Posted - July 6, 1944 STATE OF FLORIDA ) COUNTY OF DADE ) I, C. W. TOMLINSON, City Clerk in and for the City of Miami Beach, Florida, do hereby certify that Ordinance No. 714 entitled "AN ORDINANCE AMENDING SECTION 2 OF ORDINANCE NO. 592 OF THE CITY OF MIAMI BEACH, FLORIDA, KNOWN AND DESIGNATED AS THE "MIAMI BEACH BUILDING CODE, " BY ADDING THERETO, AT THE END THEREOF, AN ADDITIONAL PART TO BE KNOWN AS PART XII, " having been passed and adopted by the City Council Of the City of Miami Beach, Florida, has been posted by me in three conspicuous places in the City of Miami Beach, Florida, one of which was at the door of the City Hall in said City on the 6th day of July, A. D. 1944, and that said Ordinance remained posted for a period of at least thirty days in accordance with the requirements of the City Charter of the said City of Miami Beach. IN WITNESS WHEREOF I have hereunto set my hand and affixed the official seal of the City of Miami Beach, Florida, on this the 14th day of August, 4,, D. 1944. ` s ' City Clerk �" ORIGINAL ORDINANCE NO. 7l (Plumbing Code) A MINIMUM STANDARD FOR THE ' INSTALLATION OF PLUMBING EQUIPMENT AND APPARATUS WITHIN THE CITY OF MIAMI BEACH, FLORIDA. City Manager Claude A. Renshaw Mayor John H. Levi COUNCILMEN Wm. Burbridge Val C. Cleary Ralph Pole Herbert A. Frink Marcie Liberman D. Lee Powell J. J. FARREY CHIEF BUILDING INSPECTOR OF BUILDING DIVISION }